Tighten All Gasketed Joints; Check Chiller Tightness - Carrier AquaEdge 19XR Series Start-Up, Operation And Maintenance Instructions Manual

Single stage and two-stage semi-hermetic centrifugal liquid chillers with pic 6 controls and r-134a/r-513a 50/60 hz
Table of Contents

Advertisement

Tighten All Gasketed Joints

Gaskets normally relax by the time the chiller arrives at the job-
site. Tighten all gasketed joints to ensure a leak-tight chiller (does
not apply to refrigerant joints covered by factory insulation). Gas-
keted joints (excluding O-rings) may include joints at some or all
of the following:
waterbox covers
compressor suction elbow flanges (at compressor and at
the cooler)
compressor discharge flange
compressor discharge line spacer (both sides) if no isola-
tion valve
cooler inlet line spacer (both sides) if no isolation valve
hot gas bypass valve (both sides of valve)
hot gas bypass flange at compressor
See Tables 4 and 5 for bolt torque requirements.
BOLT SIZE
(in.)
MINIMUM
1
/
4
5
/
16
3
/
8
7
/
16
1
/
2
9
/
16
5
/
8
3
/
105
4
7
/
140
8
1
210
1
1
/
330
8
1
1
/
460
4
1
3
/
620
8
1
1
/
740
2
1
5
/
1010
8
1
3
/
1320
4
1
7
/
1630
8
2
1900
2
1
/
2180
4
2
1
/
3070
2
2
3
/
5120
4
3
6620
BOLT SIZE
(METRIC)
M4
M6
M8
M10
M12
M16
M20
M24
M27
Table 4 — Bolt Torque Requirements, Foot Pounds
SAE 2, A307 GR A
HEX HEAD
NO MARKS
LOW CARBON STEEL
MAXIMUM
4
6
8
11
13
19
21
30
32
45
46
65
65
95
150
200
300
475
660
885
1060
1450
1890
2340
2720
3120
4380
7320
9460
Table 5 — Bolt Torque Requirements, Foot Pounds (Metric Bolts)
CLASS 8.8
MINIMUM
1.75
6
14
28
48
118
230
400
580

Check Chiller Tightness

Figure 26 outlines the proper sequence and procedures for leak
testing.
The 19XR chillers are shipped with the refrigerant contained in
the condenser shell and the oil charge in the compressor. The cool-
er is shipped with a small positive pressure refrigerant holding
charge. Units may be ordered with the refrigerant shipped sepa-
rately, along with a 15 psig (103 kPa) nitrogen-holding charge in
each vessel.
To determine if there are any leaks, the chiller should be charged
with refrigerant. Use an electronic leak detector to check all flang-
es and solder joints after the chiller is pressurized. If any leaks are
detected, follow the leak test procedure (page 26).
If the chiller is spring isolated, keep all springs blocked in both di-
rections to prevent possible piping stress and damage during the
transfer of refrigerant from vessel to vessel during the leak test
process, or any time refrigerant is being transferred. Adjust the
springs when the refrigerant is in operating condition and the wa-
ter circuits are full.
SAE 5
SOCKET HEAD OR HEX
WITH 3 RADIAL LINES, OR SA499
MEDIUM CARBON STEEL
MINIMUM
MAXIMUM
6
13
18
22
31
35
50
53
75
75
110
105
150
175
250
265
380
410
580
545
780
770
1,100
1,020
1,460
1,220
1,750
1,670
2,390
2,180
3,110
2,930
4,190
3,150
4,500
4,550
6,500
5,000
7,140
8,460
12,090
11,040
15,770
MAXIMUM
2.5
9
20
40
70
170
330
570
830
24
SAE 8
HEX HEAD
WITH 6 RADIAL LINES OR
SA354 GR BD
MEDIUM CARBON STEEL
MINIMUM
9
9
20
32
53
80
115
160
260
415
625
985
1,380
1,840
2,200
3,020
3,930
5,280
5,670
8,200
11,350
15,710
19,900
CLASS 10.9
MINIMUM
MAXIMUM
2.5
8
20
40
70
170
330
570
820
MAXIMUM
13
28
46
75
115
165
225
370
590
893
1,410
1,960
2,630
3,150
4,310
5,610
7,550
8,100
11,710
16,210
22,440
28,440
3.5
12
30
57
100
240
470
810
1175

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents