Carrier AquaEdge 19XR Series Start-Up, Operation And Maintenance Instructions Manual page 122

Single stage and two-stage semi-hermetic centrifugal liquid chillers with pic 6 controls and r-134a/r-513a 50/60 hz
Table of Contents

Advertisement

19XR PIC 6 OPTION CONFIGURATION TABLE (CONF_OPT) CONFIGURATION SHEET
DESCRIPTION
Auto Restart Option
Common Sensor Option
EC Valve Option
0 = No, 1= Cont
2 = On/Off, 3 = 4-20 mA
EC Valve Selection
0 = Disable, 1 = Surge
2 = Low Load, 3 = Comb
ECV Open IGV1 Position
ECV Close IGV1 Position
ECV Off DT for Low Load
ECV On DT for Low Load
ECV Low Load DB
Head Pres Valve Option
Head Pres Delta P 0%
Head Pres Delta P 100%
Head Pressure Min Output
Head Pressure Deadband,
Tower Fan High set point
Refrigerant Leak Option
Refrig Leakage Alarm mA
Oil EXV Option
Oil Temp High Threshold
Oil Temp Low Threshold
Gas Torque Factor
Guide Vane/SRD Factor
Power Recovery Timeout
Condenser Flush Alert
Customer Alert Option
Ice Build Option
Ice Build Recycle
Ice Build Termin Source
0 = Temp, 1 = Contact, 2 = Both
Water Pressure Option
0=No, 1=Pres., 2=Pres. D.
Water Flow Measurement
0 = No, 1 = Flow Meter, 2 = Flow
Switch
Water Flow Determination
0=Sat Temp, 1=Flow Switch.
Water Flow Determination(
0=Sat Temp, 1=Flow Switch)
Water Flow at 4 mA
Water Flow at 20mA
Evap Flow Rate Baseline
Evap Pres Drop Baseline
Cond Flow Rate Baseline
Cond Pres Drop Baseline
Water Pres Drop @ 20mA
Vapor Source SV Delay
Max Oil Pressure Diff
Oil Pump VFD Max Step
Vapor Source SV Delay
Vapor Source SV Option
Evap Liquid Temp Opt
Evap App Calc Selection
Sat Temp = 0, Ref Temp = 1
Remote Stop Contact
RANGE
UNITS
DSABLE/ENABLE
DSABLE/ENABLE
0 to 3
0 to 3
0.5 to 10
1.5 to 20
0.5 to 10.0
0.5 to 10.0
0.5 to 2.0
DSABLE/ENABLE
20.0 to 85.0
20.0 to 85.0
0.0 to 100.0
0-10
55 to 105
DSABLE/ENABLE
4 to 20
DSABLE/ENABLE
100 to 140
90 to 130
0.25 to 3.0
0.7 to 1.20
0 to 60
DSABLE/ENABLE
DSABLE/ENABLE
DSABLE/ENABLE
DSABLE/ENABLE
0 to 2
0-2,0,
0-2
0-1
0-1
0-12000
0-12000
0-9000
0-20
0-9000
0-20
0-40
0-10
35-60
0-10
0-10
DSABLE/ENABLE
DSABLE/ENABLE
0/1
DSABLE/ENABLE
CL-6
DEFAULT
DSABLE
DSABLE
0
0
%
5.0
%
10.0
^F
4.0
^F
2.0
^F
1.0
DSABLE
psig
25.0
psig
50.0
%
0.0
1
75
DSABLE
20
mA
DSABLE
°F
120
°F
110
°F
1
0.95
min
15
DSABLE
DSABLE
DSABLE
DSABLE
0
0
0
0
GPM
0.00
GPM
0.00
GPM
0.00
PSI
0.00
GPM
0.00
PSI
0.00
PSI
10.00
min
5.0
PSI
50
%
7
min
5
DSABLE
Enable
1
DSABLE
VALUE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents