Gira DALI Gateway Product Documentation page 46

Table of Contents

Advertisement

Setting the status messaging function for the manual control mode
The DALI Gateway can transmit a status message to the bus via a separate object with either activated
or deactivated manual control mode. The status telegram can only be transmitted with the bus voltage
switched on. The polarity of the status telegram can be parameterized.
The manual control during bus mode must be enabled.
Set the "Transmit manual control status?" parameter on the "Manual control" parameter page to
"yes".
The status messaging function of the manual control is enabled and the status object becomes
visible.
Specify for the "Function and polarity of status object" parameter whether the status telegram is
generally a "1" telegram every time the manual control mode is activated or only in those cases when
the permanent manual control is activated.
The status object is always "0", when the manual control mode is deactivated.
The status will be actively transmitted to the bus ("0") only if a manual control that was activated
during bus voltage failure has been terminated by the bus voltage return. In this case, the status
telegram will be transmitted without delay.
If an active manual control is terminated by a disable, the actuator will also transmit a "Manual
control inactive" status telegram to the bus.
Setting a bus mode disable
Individual DALI groups can be disabled locally. The affected groups can then no longer be controlled
via the KNX/EIB. A bus mode disable is effected by local control in permanent manual control mode
and indicated by the flashing of the group number in the 7-segment display. The disabled groups can
then only be addressed in permanent manual control mode.
The manual control during bus mode must enabled.
Set the "Bus mode of individual groups can be disabled?" parameter on the "Manual control"
parameter page to "yes".
The bus mode disable function is enabled and can be activated locally. If "No" is selected for this
parameter, the bus mode disable cannot be activated in permanent manual control mode.
A locally activated disable has the highest priority. Other functions of the Gateway that can be
activated via the bus (e.g. forced-control position or disable function) will then be overridden.
Depending on the ETS parameterization of the Gateway, the groups will be set to the state last
adjusted via manual control or to the state internally tracked (direct operation, forced-control position,
disable lock) when the permanent manual control has been enabled and switched off afterwards.
A locally activated bus mode disable will not be reset in case of bus voltage failure or bus voltage
return. A supply voltage failure (mains voltage failure) or an ETS programming operation will always
deactivate the bus mode disable.
Best. Nr. 1060 00
"DALI Gateway C00CX2 EN / C00CX4 EN" software
Functional description
Page 46 of 136

Advertisement

Table of Contents
loading

Table of Contents