Applications
Connect tool
Note:
12 / 24
Siemens
Building Technologies
RDF880KN... thermostats are for VRF HMI and heating applications.
Configure or changing parameter settings during commissioning using one of the
following tools:
-
Local HMI
-
Synco ACS
-
ETS4/5
Connect the Synco ACS or ETS tools to the KNX bus cable at any point for
commissioning:
KNX
L
X1
M X2
CE+ CE-
N
Q11 Q14
Q12
RDF880KN...
ACS and ETS4/5 require an interface:
-
RS232 KNX interface (such as Siemens N148 / UP146 / UP152)
-
OCI700 or OCI702 USB-KNX interface
An external KNX bus power supply is required if an RDF880KN/NF is connected
directly to a tool (ACS or ETS4/5) via KNX interface.
RDF880KN...
Touch Screen Flush-mount Room Thermostats with KNX Communications
Siemens
N148 /
UP146 /
UP152
RS232
ETS
ETS / ACS
A6V11282546_en--_a
Siemens
OCI700
or
OCI702
2018-04-19