Commissioning notes
Before power up
Wizard function
10 / 24
Siemens
Building Technologies
Select DIP switch setting is required for RDF880KN... thermostats.
COMMISSIONING: Download via ETS
1. DIP switch setting
All in OFF positions
3. Touch & hold this
icon > 5 s to enter
Programming mode
COMMISSIONING: Local via DIP Switches
1. Set application via
DIP switches
2. Configure basic
control parameters
via Wizard
See Configure Parameters
via Wizard in Wizard function.
After power up, the wizard function guides users to configure the basic parameters
for normal operation according to the table below.
Touch ƒ / „ to advance / return to any parameter;
Touch + / - to select any desired available values.
RDF880KN...
Touch Screen Flush-mount Room Thermostats with KNX Communications
2. First power up
Press to turn ON
4. Ready for downloading
address & application
Touch "ON" to exit
DIP switch
positions
APPLICATION
1
2
ON
ON
VRF+FLOOR HEAT
OFF
ON
ON
OFF
FLOOR HEAT ONLY
VRF ONLY
A6V11282546_en--_a
2018-04-19