(4) AC/DC Drive object (Class 2A hex.)
This object monitors the current speed command settings and the current speed of the inverter, and configures
their related settings. It also monitors the output data issued from the inverter.
Instance
Attribute
1
03 hex
AtReference
04 hex
NetRef
06 hex
DriveMode
07 hex
SpeedActual
08 hex
SpeedRef
09 hex
CurrentActual
11 hex
OutputVoltage
12 hex
AccelTime
13 hex
DeccelTime
14 hex
LowSpdLimit
15 hex
HighSpdLimit
16 hex
SpeedScale
17 hex
CurrentScale
1B hex
VoltageScale
1C hex
TimeScale
1D hex
RefFromNet
*
"Read-only" while the inverter is running.
Name
Description
Speed arrival
Switching speed command
source
Run mode. Fixed at 0.
Speed monitor (r/min)
Speed command (r/min)
Output current
(in units of 0.1 A)
Output voltage (V)
Acceleration time (ms)
Deceleration time (ms)
Lower limit speed (r/min)
Maximum speed (r/min)
Change the speed scale
(r/min)
all
calculated below.
r/min
SpeedScale
2
Change the current scale
(0.1 A) all at once, as
calculated below.
0.1
A
CurrentSca
le
2
Change the voltage scale (V)
all at once, as calculated
below.
V
VoltageSca
le
2
Change the time scale (ms)
all at once, as calculated
below.
ms
TimeScale
2
Current speed command
source
Value (hex.)
00: Stopped or
Accelerating/
decelerating
01: Speed arrival
00: Inverter
01: DeviceNet
00: Unique to vendor
Actual speed
-32768 to 32767 r/min
Output current
Output voltage
0 to 65535 ms
0 to 65535 ms
0 to 32767 r/min
0 to 32767 r/min
-15 to 15
at
once,
as
(Factory default: 0)
-15 to 15
(Factory default: 0)
-15 to 15
(Factory default: 0)
-15 to 15
(Factory default: 0)
00: Inverter
01: DeviceNet
30
R/W
Data size
R
Byte
R/W
Byte
R
Byte
R
Word
R/W
Word
R
Word
R
Word
R/W
Word
R/W
Word
R/W
Word
R/W *
Word
R/W
Byte
R/W
Byte
R/W
Byte
R/W
Byte
R
Byte