User-defined function code 1: Monitored data of function code specified by o48
Access to function code (number):
Access to function code (group):
Access to function code (read data): Value read from the specified function code when requested
Access to function code (error code): Error code displayed (see Table 7.3) when requested read/write is
Others:
Error code
Upper
Lower
1F
02
No function code (in writing)
03
Function code not allowed to change
06
Not allowed to change in running
07
Not allowed to change with X terminal
being ON
08
Data entry range error
0F
Function code data being written
21
No function code (in reading)
(3) Examples for writing and reading to/from function codes
Normal writing and reading
This example shows communication data for writing to function code F03 (=0403h) to change the data from
factory default 60.0 Hz (=0258h) to 300.0 Hz (=0BB8h) and then reading from F03. (The following data is
expressed in hexadecimal.)
Select the inverter's function code F03.
Write: 00 00 00 00 03 04 00 00
Read: 28 10 00 00 00 00 00 00
Input data to F03.
Write: 00 00 00 00 03 04 B8 0B
Read: 28 10 00 00 00 00 00 00
Write data into F03.
Write: 00 10 00 00 03 04 B8 0B
Read: 28 10 00 00 03 04 B8 0B
Read from F03.
Write: 00 08 00 00 03 04 00 00
Read: 28 10 00 00 03 04 B8 0B
Reading/writing error
This example shows communication data that returns an error code since writing and reading to/from
nonexistent function code F99 (=0463h) is attempted.
Select the inverter's function code F99.
Write: 00 00 00 00 63 04 00 00
Read: 28 10 00 00 00 00 00 00
Write data into F99.
Write: 00 10 00 00 63 04 00 00
Read: 28 50 00 00 63 04 02 1F
Read from F99.
Write: 00 08 00 00 63 04 00 00
Read: 28 50 00 00 63 04 21 1F
(e.g., speed monitor M06, M09, M79. etc.)
Value specified by "Request for access to function codes" instance
Value specified by "Request for access to function codes" instance
read/write is normal
abnormal
Same as for input instance 101.
Table 7.3 Error Code List
Error name
Attempted to write to a nonexistent function code.
Attempted to write to a read-only function code.
Attempted to write to a function code not allowed to
change when the inverter is running.
Attempted to write to a function code not allowed to
change when X terminal is ON.
Attempted to write data out of the range.
Requested to write to a function code being written.
Attempted to read from a nonexistent function code.