Installation and Operation Guide SOLECTRIA XGI 1000 (Rev D)
Figure 3-21 Sample Network Configurations with Weather Station and DAS
Connecting Multiple Inverters
To connect multiple inverters together, set up an Ethernet daisy chain (see Figure 3-22), star configuration using
Ethernet switches, or a tree configuration (mixed network) (see Figure 3-23).
The maximum number of inverters in any single daisy chain is 50 inverters.
When using star configuration architecture, the maximum number of inverters from one end of a daisy
chain to the end of any other daisy chain must not exceed 50 inverters.
Use a shielded Cat6 cable with max length 328 ft. (100m) for all ethernet connections.
Figure 3-22 SOLECTRA XGI Inverters Connected with Ethernet Daisy Chain
DOCR-070733-D
Page 35 of 86