Outdoor and Indoor Stacks
The outdoor and indoor stacks are optional equipment and
do not come standard with the heater. Refer to installation
instructions inside box for instructions on how to install
outdoor/indoor stack.
Model
Outdoor Stack
206A
009834
266/266A
009835
336A
009836
399/406A
009837
Table D.
Outdoor and Indoor Stack Kit Number
OUTDOOR STACK KIT
(1) Outdoor, painted
(1) Adapter plate
(3) Mounting brackets (clips)
(1) Top panel cover
(2) 1-foot sections of metal tape
(3) Screws
(1) Instructions
Figure 6.
Outdoor Stack Kit Components
NOTE: The outdoor drafthood kit does not require any
additional vent pipe for proper operation. This drafthood
functions as the vent termination.
INDOOR STACK KIT
(1) Drafthood, unpainted
(1) Adapter plate
(3) Mounting brackets (clips)
(3) Screws
(1) Instructions
Figure 7.
Indoor Stack Kit Components
Indoor Stack
009838
009839
009840
009841
Clips
Clips

Combustion and Ventilation Air

Indoor Units Only
The heater must have both combustion and ventilation
air. The minimum requirements are listed in the latest
edition of the National Fuel Gas Code (U.S. ANSI Z223.1
or Canada CAN/CSA-B149) and any local codes that
may have jurisdiction. The most common approach is
the "2-opening" method, with combustion air opening no
more than 12" from the floor and the ventilation opening
no more than 12" from the ceiling. For opening sizes
using this method, see below.
All Air from Inside the Building:
Each opening shall have a minimum net free area as noted:
Model
206A
266/266A
336A
399/406A
Table E.
Opening Minimum Net Free Requirements -
Indoor Air
All Air from Outdoors:
When air is supplied directly from outside the building, each
opening shall have a minimum net free area as noted:
Unrestricted
Typical Screened or
Model
Opening
sq. in. (m 2 )
206A
50 (0.03)
266/266A
67 (0.04)
336A
84 (0.05)
399/406A
100 (0.06)
Table F.
Opening Minimum Net Free Requirements -
Outdoor Air
A
CAUTION: Combustion air must not be contaminated
by corrosive chemical fumes which can damage the
heater. Such damage will not be covered by the warranty.
Sq. in. (m
)
2
200 (0.13)
266 (0.17)
333 (0.21)
399 (0.26)
Typical Screened
and Louvered
Louvered Opening
Opening
sq. in. (m 2 )
sq. in. (m 2 )
75 (0.05)
100 (0.06)
101 (0.06)
134 (0.09)
126 (0.08)
168 (0.11)
150 (0.1)
200 (0.13)
11