Output; Signal On Alarm; Connectable Load; Switch Behaviour - Endress+Hauser Soliphant T FTM260 Technical Information

Cost-effective vibration limit switch for fine-grained solids
Table of Contents

Advertisement

Signal on alarm

Connectable load

Switch behaviour

Fail-safe mode

4

Output

Output open or relay de-energised
• with FEM31
(The load is switched directly via a thyristor in the power circuit)
Short-term (40 ms) max. 1.5 A, max. 375 VA at 250 V or max. 36 VA at 24 V
(no short circuit protection),
continuous max. 87 VA at 253 V, max. 8.4 VA at 24 V,
min. 2.5 VA at 253 V (10 mA), min. 0.5 VA at 24 V (20 mA);
Voltage drop across FEM 31 max. 12 V at load current >10 mA
(max. 10 V at load current >20 mA);
Quiescent current max. 3.8 mA with open thyristor
• with FEM32
(The load is switched via a transistor and separate PNP connection)
Short-term (1 s) max. 1 A, max. 55 V
(cyclic overload and short-circuit protection),
continuous max. 350 mA,
max. 0.5 µF at 55 V, max. 1.0 µF at 24 V;
Residual voltage <3 V (with closed transistor);
Residual current <100 µA (with open transistor)
• with FEM34
(The load switched via a potential-free changeover contact)
I~ max. 6 A, U~ max. 253 V,
P~ max. 1500 VA, cos ϕ = 1, P~ max. 750 VA, cos ϕ > 0.7;
I– max. 6 A bis 30 V, I– max. 0.2 A to 125 V;
Additional switching delay 0.3 s
approx. 0.6 s when covered,
approx. 1.4 s when free
Minimum or maximum fail-safe mode, switchable