Controls - Gas Valve Suf 199 And 250; Adjustment Procedure; Gas Pressure; Suf 199 And 250 Models - State Water Heaters SUF 130 300 Service Handbook

High efficiency commercial gas series
Hide thumbs Also See for SUF 130 300:
Table of Contents

Advertisement

ULTRAFORCE COMMERCIAL GAS WATER HEATER
CONTROLS – GAS VALVE SUF 199 and 250

ADJUSTMENT PROCEDURE:

GAS PRESSURE

SUF 199 AND 250 MODELS

IMPORTANT NOTE
THE SUF 199 AND 250 MODELS
INCORPORATE A NEW GAS CONTROL,
WHICH OPERATES AT A MANIFOLD
PRESSURE OF 0"W.C. (0 kPa) FOR BOTH
NATURAL AND PROPANE GAS. SEE THE
GAS PRESSURE CHART ON PAGE 4.
THESE MODELS ARE CONFIGURED
PRIOR TO BEING SHIPPED FROM THE
FACTORY AND NO ADJUSTMENTS ARE
NECESSARY PRIOR TO STARTUP. THE
CONTROLLER MONITORS THE AIR FLOW
AND MAKES ADJUSTMENTS TO THE FAN
SPEED WHICH IN EFFECT CONTROLS
THE AMOUNT OF GAS FLOW.
THEREFORE, THE UNIT WILL SELF
ADJUST TO ACQUIRE THE CORRECT
AMOUNT OF INPUT.
Supply gas pressure to the water heater for
natural gas should be between a maximum
of 10.5" (2.59kPa for natural gas) W.C.
(14.0"/3.45kPa for propane) and a minimum
as shown on page 4: that is, for Natural Gas
4" (.98kPa) W.C. And 9.0" (1.97kPa) for
Propane Gas. The inlet gas pressure must
not exceed the maximum value.
A supply gas pressure
(service regulator) must be installed on
the gas supply line within 10' (305 cm)
of the unit.
State Water Heaters – Technical Training Department 24
SUF 120 thru 400 SERVICE HANDBOOK
regulator
Servicing should only be performed by a Qualified Service Agent
Once the unit is installed and filled with water
and the in let p ressures c onfirmed, s imply
turn the switch "on" and observe operation.
Cycle the unit "off" and "on" several times to
ensure proper operation.
HIGH ALTITUDE INSTALLATION
The SUF 199 and 250 models are suitable
for installation up to 10,100 feet above sea
level with no adjustments.
GAS ORIFICE
The SUF 199 and 250 models do not have a
natural gas orifice. A .230" orifice is used on
LP gas models.
Gas Control Without Orifice
Natural Gas
Gas Control with .230" LP Orifice
Ashland City, Tennessee © 2009
Venturi
Gasket
w/o orifice
Venturi
Gasket w/
LP Gas
Orifice
(.230"
Brass)
198152-002

Advertisement

Table of Contents
loading

This manual is also suitable for:

Suf100199Suf 60 120Suf 100 150Suf 100 199Suf 100 250

Table of Contents