ULTRAFORCE COMMERCIAL GAS WATER HEATER
CONTROLS – PRESSURE SWITCHES – ALL MODELS
All SUF models are provided with four pressure
switches. T hese s witches ar e es sential to the
safe an d pr oper op eration o f the uni t. T he
switches are wired to the c entral c ontrol board
(CCB)
individually an d ea ch i s monitored
individually. The (CCB) is set up to shut the unit
down w henever there i s a failure of any of the
switches and declare a fault for each individual
switch. It is important to understand the purpose
of each switch.
Low Gas Pressure
Sw itch
BLOWER PROVING SWITCH
The Blower Proving S witch i s pr ovided on t he
heater t o v erify that t he f an i s op erating. It i s a
positive pr essure s witch w hose electrical c ontacts
are normally open. Th e blower p roving switch
electrical contacts will close on a rise in pressure
as the blower increases the pressure in the burner.
This s witch i s c onnected t o t he b urner t ap b y a
piece of Tygon (s oft pl astic) t ubing. This t ubing
must be connected in order for the switch to close
the el ectrical contacts. The controller requires that
the el ectrical contacts on t his p ressure switch b e
open before it will allow the blower to come on. The
control w ill declare a f ault on the U IM if ei ther
condition occurs.
State Water Heaters – Technical Training Department 27
SUF 120 thru 400 SERVICE HANDBOOK
Pressure
Sw itches
Servicing should only be performed by a Qualified Service Agent
BLOCKED OUTLET PROVING SWITCH
The blocked outlet proving switch electrical contacts
are normally closed. The blocked outlet proving
switch el ectrical c ontacts w ill open on a rise in
pressure. Check t o see i f t he c ondensate i s
allowed to flow freely from the exhaust elbow and
for obstructions in the exhaust venting and exhaust
vent t erminal. Also c heck the t hat t he equivalent
feet of vent pipe for the specific model has not been
exceeded. Check the vent length tables on page 9
BLOCKED INLET PROVING SWITCH
The Blocked Inlet Proving switch electrical contacts
are normally closed. The bl ocked i nlet pr oving
switch el ectrical c ontacts w ill op en when an
increase in negative pressure (vacuum) occurs
in the intake vent pipe. The switch is connected to
the pr essure tap o n the PVC flange connected to
the i nlet of the b lower. W hen this switch pr events
the u nit f rom ig niting, most li kely the in take is
blocked by some means. Verify that the air intake
pipe and ai r i ntake v ent t erminal ar e f ree of
obstructions that may prevent air from entering the
unit. Also check the that the equivalent feet of vent
pipe for the specific model has not been exceeded.
Check the vent length tables on page 9
LOW GAS PRESSURE SWITCH
The Low Gas Pressure Switch electrical contacts
are normally open. The low gas pressure switch
electrical c ontacts w ill close on a rise pressure.
The c ontacts w ill open w hen t he p ressure falls
below the fixed set point. If this happens during a
heating cycle a the burner will be shut down and a
fault will be declared on the UIM.