Chapter 4 – Twelve–Pulse Serial / Sequential Configurations with DCS 600
4 - 16
II F2
Voltage measurement
The voltage measurement can be done by high ohmic hardware
(solution 1) or by AC and DC transducer (solution 2), but the
scaling is different from the usual 12-pulse serial configuration.
Solution 1 for sandwich configuration:
Rated line (supply)
voltage [V]
200 ... 500 **)
500 ... 600
500 ... 690
690 ... 800
800 ... 1000
*)
See Manual „Technical Data" (resistors W1 ... W 26)
**) No changes of voltage coding are required for 400 V and 500 V
standard converters of size C4!
Solution 2 for sandwich configuration:
Rated line
(supply)
voltage
[V]
200 ... 500
500 (6 – 12 – 18)
500 ... 600
600 (7 – 13 – 19)
600 ... 690
690 (8 – 14 – 20)
690 ... 800
790 (9 – 15 – 21)
800 ... 1000
1000 (10 – 17 – 23)
*)
Terminals of part No. 3AST 47 8002 D1
**) Position of part No. DCA 001 9214
SDCS-PIN-51
voltage coding *)
500
600
690
790
1000
Hardware
Terminals / Settings
AC transducer
[terminals *)]
DCS 600 Manual for 12 – Pulse Operation
Software coding
S CON NOM VOLT
(42.08)
500
600
690
800
1000
Software
coding
S CON
NOM VOLT
DC transducer
(42.08)
[position **)]
675 (6)
500
810 (5)
600
945 (4)
690
1080 (3)
800
1350 (1)
1000