DCS 600 Manual for 12 – Pulse Operation
Chapter 4 – Twelve–Pulse Serial / Sequential Configurations with DCS 600
In the serial and sequential mode the software signals relevant to
the voltage are rescaled according to the doubled output voltage of
the configuration. This rescaling is valid for the master and the
slave as well. The monitoring of the signals is different depending
on whether CDP 312 / DriveWindow or APC / AC 80 is used.
The motor terminal voltage is shown by the following signals:
RL ARM VOLT ACT (1.13)
ARM VOLT ACT (1.14)
RL EMF VOLT ACT (1.17)
EMF VOLT ACT (1.18)
Hardware
x
DC voltage
measurement
ADJ UDC
135 % U
[4096]
S
2.7 x U
(42.06)
supply
2 V equals 2 V
(CDP 312 / DriveWindow)
[1] equals 2 V
(APC / AC 80)
135 % U
[3786]
S
2.7 x U
(42.06)
supply
2 V equals 2 V
(CDP 312 / DriveWindow)
[1] equals 2 V
(APC / AC 80)
EMF control
EMF feedback
APC
Fieldbus
[1] = 2
Advant
x2
DriveWindow
CDP 312
Display of
real values
equals
equals
(1.14)
(1.18)
(1.14)
(1.18)
Figure 4/6
4 - 13
II F2