Twelve-Pulse Serial / Sequential Software Configurations; Pulse Com- Munication Via Sdcs-Con-2 Channel V260 (12 - Pulse Link); Dataset For 12 - Pulse Serial / Sequential Mode; Pulse Software Configuration For Serial / Sequential Mode - ABB DCS 600 MultiDrive Series Manual

Dcs thyristor power converters for dc drive systems 25 to 5150 a/10300 a. manual for 12 – pulse operation parallel/serial/sequential
Hide thumbs Also See for DCS 600 MultiDrive Series:
Table of Contents

Advertisement

4.2 Twelve–pulse serial / sequential software configurations
12 – pulse com-
munication via
SDCS-CON-2 channel
V260
(12 – pulse link)
Dataset for 12 –
pulse serial / sequen-
tial mode
12 – pulse Software
configuration for se-
rial / sequential mode
Parallel
mode
Serial/sequential 〉
mode
DCS 600 Manual for 12 – Pulse Operation
Chapter 4 – Twelve–Pulse Serial / Sequential Configurations with DCS 600
The DC thyristor power converters from the DCS 600 series are
equipped with a separate optical fibre DDCS link on the SDCS-
CON-2 board for the 12 – pulse communication (V260, located
close to connector X7). No other communication setup is required,
except a communication timeout parameter
This parameter defines the allowed number of control cy-
(47.09).
cles (3.3 ms at 50 Hz) without receiving a valid message. For the
12 – pulse slave, this parameter must be set from default value
to at least "4".
One DDCS dataset in each direction is exchanged between the two
converters. Their content is:
12 – pulse Master
3.09
Control status of
12 – pulse master
1.13
Act. armature voltage
2.24
Firing angle of slave
3.10
Control status of
12 – pulse slave
2
2.21
)
Act. armature current
of 12 – pulse slave
---
Act. armature voltage
of slave
1
) This AMC-table index exists in Software versions 15.605 or later
2
) 100 % = I
rated motor
The 12 – pulse Software configuration is based on a 12 – pulse
master converter and a 12 – pulse slave converter.
This is done by setting function specific (master/slave) parameters
and signals (the 12 – pulse related signals and parameters are
mentioned within this chapter; 12 – pulse parameters are mainly
inside parameter group 57).
The 12 – pulse mode is activated by setting the desired control
mode to parameter:
OPER MODE 
SELECT
(15.16)
rescaled from the master setting
0:
6P SINGLE
1:
12P PAR MAS
2:
12P PAR SLA
3:
12P SER MAS
4:
12P SER SLA
5:
FIELD EXC
COMM TIMEOUT 12P
12 – pulse Slave
Control status of
12 – pulse master
Act. armature voltage
of master
Firing angle reference
Control status of
12 – pulse slave
Act. converter current
Act. armature voltage
6–pulse operation
12–pulse parallel master
12–pulse parallel slave
12–pulse serial master
12–pulse serial slave
Field exciter mode
"1"
3.09
---
3.13
3.10
1.15
1.13
4 - 3
II F2