Boulter Buderus Benchmark 600-28C Installation And Servicing Instruction page 9

Wall-mounted condensing gas boiler
Table of Contents

Advertisement

Installation
1.3.2
Air supply and flue gas exhaust in a closed
installation
A ventilation cover is integrated into the 600 Series condensing
gas boilers. This cover houses a number of components, such
as the burner and the heat exchanger. Since this ventilation
cover is part of the air supply system, it is vital that it is always
installed correctly.
To ensure optimal operation, the 600 Series appliances must
be connected to a Buderus horizontal or vertical flue terminal.
These terminals have been developed specifically for the 600
Series condensing gas boilers and have been comprehen-
sively tested. The Buderus horizontal or vertical flue terminal
kits ensure trouble-free operation.
Horizontal flue pack:
– pos. 1: 1 Flue turret 80/125 to 60/100 (NE 87603);
– pos. 2: 1 Horizontal flue terminal 60/100;
– pos. 3: 1 Flue finishing kit.
1.3.3
Maximum Flue length
The maximum pipe length of the air supply and flue gas
exhaust pipes for the 600 Series condensing gas boilers (see
table 2) is determined by the total pressure loss of all compo-
nents in the flue gas exhaust / air supply system.
Flow pressure available for use [Pa]
600 - 28C
Take the flue pipe clearances into account when planning the
layout of the place of installation (see see subsection 1.3.1:
"Siting the flue terminal" on page 8).
Maximum wall thickness without extensions is 550 mm.
Maintain a minimum side of 100 mm (see fig. 3).
1.3.4
Additional flue parts
Additional flue parts (see table 3) can be ordered from your
supplier.
Subject to modifications resulting from technical improvements!
Installation and maintenance instructions for wall-mounted condensing gas boiler 600 - 28C • 01/2004
10
60/100
80/125
1
fig. 2
Horizontal flue pack
fig. 3
Side flue and rear flue installation
Maximum
Boiler 600 - 28C
pipe length
for 60/100
L = 12.0 m
Table 2
Pipe length
Flue parts
Concentric pipe, 500 mm long,
adjustable, 60/100
Concentric pipe, 1000 mm long,
not adjustable, 60/100
Concentric bend 90°, 60/100
Concentric bend 45°, 60/100
Vertical flue turret adaptor 80/125 to 60/100
Table 3
Additional flue parts
Boulter Buderus Ltd. • http://www.boulter-boilers.com
1
2
3
L
550 mm
50 mm
For every 90° bend the
maximum pipe length has to
be reduced by
1.4 m
Order No.
NE 83703
NE 83704
NE 83705
NE 83706
9