Boulter Buderus Benchmark 600-28C Installation And Servicing Instruction page 52

Wall-mounted condensing gas boiler
Table of Contents

Advertisement

5
Servicing
5.3.8
Checking the bi-sensor, return sensor and
hot water sensors.
Remove the cable connection (see fig. 74) of the bi-sensor.
Measure the resistance of both parts of the bi-sensor
(see fig. 75).
Disconnect the return sensor (see fig. 76).
Subject to modifications resulting from technical improvements!
52
Installation and maintenance instructions for wall-mounted condensing gas boiler 600 - 28C • 01/2004
fig. 74 Remove cable connection of bi-sensor
fig. 75 Measure resistance of bi-sensor
fig. 76 Disconnect return sensor
Boulter Buderus Ltd. • http://www.boulter-boilers.com

Advertisement

Table of Contents
loading

This manual is also suitable for:

Benchmark 600 series

Table of Contents