Initial start-up
Set the boiler in service mode by pressing the chimney
sweep button until a non-blinking LED appears in the lower
right hand corner of the display.
Press the chimney sweep button and the service button at
the same time, until "L--." appears in the display.
Write down the set heating capacity.
Adjust the heating capacity to "L25." by pressing the reset
button.
Confirm by pressing the service button.
Measuring the ionisation current. The ionisation current
being checked must measure >2 µA direct current.
Enter the reading on the report form.
Set the mains power switch to "0" (fig. 41, item 1).
Remove multimeter and restore the plug-and-socket
connection to its original state.
Refit the ventilation cover.
Refit the casing and the safety screw (fig. 48, item 1).
Set the mains power switch to "1" (fig. 41, item 1).
Reset the heating capacity to the desired capacity (see
subsection 2.1.3: "Setting the heating capacity").
2.1.12 Handing over
After completing the installation and commissioning of the
system the installer should hand over to the householder by
the following actions:
Hand the user manual to the householder and explain
his/her responsibilities under the relevant national regula-
tions.
Explain and demonstrate the lighting and shutting down
procedures.
Subject to modifications resulting from technical improvements!
Installation and maintenance instructions for wall-mounted condensing gas boiler 600 - 28C • 01/2004
fig. 48 Refit casing and safety screw