7215 3000 - 03/2005 GB/IE(EN) For the installer Installation and maintenance instructions Wall-mounted condensing gas system boiler Buderus 500 - 24/S Please read thoroughly...
Page 2
If you have suggestions for improvement or have found discrepancies, please do not hesitate to contact us. Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
– service instructions; BENCHMARK' Log Book – wall spacing frame instructions. All Boulter Buderus gas fired boilers now include an installation, commissioning and service record log book. The details of the log book will be required in the event of any warranty work being requested.
Page 4
An existing cupboard or compartment may be used, provided overriding statutory obligations. that it is modified for the purpose. The design and construction of the Boulter Buderus wall- In both cases, details of essential features of cupboard/ mounted condensing gas system boiler 500-24/S conforms to...
Page 5
Wall-mounted condensing gas system boilers must only be The domestic hot water service must be in operated with Boulter Buderus purpose made gas systems, accordance with BS 5546 and BS 6700. which are certified for this type of boiler.
Page 6
Abbreviations = Air Vent = Boulter Buderus cylinder thermostat = Boulter Buderus diverter valve = Connection Block = Central Heating = Central Heating Flow = Central Heating Return...
Condensate water outlet Ø mm 21.5 Pressure relief valve (compression fitting) Ø mm 15 (adapter supplied with boiler) Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 8
Boiler dimensions and weight Height x Width x Depth 780 x 460 x 330 Weight (without casing) Casing Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
NOTE See wall-mounting template for the necessary clearances. The wall spacing frame may not always be necessary. Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Connect pipes as shown in fig. 4. Ensure that all pipework is routed so as to minimise any strain on the boiler fittings. Boulter Buderus advises to use copper piping for the first 600 mm, then it is allowed to switch to another approved pipe material.
Page 12
It should be noted that the connection of a condensate pipe to a drain may be subject to local building controls. Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 13
9 External termination of condensate drainage pipe via internal discharge branch (e.g. sink waste) and condensate syphon Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 14
50 mm from bottom of tube and facing away from house fig. 11 External termination of condensate drainage pipe to absorption point Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
MUST NOT be closer than 25 mm to combustible material. Detailed recommendations on the protection of combustible material are given in BS. 5440- 1:2000. Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 16
To ensure optimal operation, the 500 Series appliances must be connected to a Boulter Buderus horizontal or vertical flue terminal. These terminals have been developed specifically for Boulter Buderus condensing gas boilers and have been comprehensively tested for trouble free operation when correctly installed.
Page 17
Maximum wall thickness without extensions is 415 mm. Maintain a minimum side clearance of 8 mm (see fig. 14). fig. 16 Vertical flue length Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 18
80/125 flue gas systems, because the flue outlet of the boiler is 60/100. Weathering slates for 60/100 and 80/125 Flat roof, pitched roof. Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 19
Fit the horizontal flue turret (fig. 19) onto the appliance flue connector. Flue gas testing point fig. 19 Horizontal flue turret with flue gas testing point Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 20
Outer terminal relative Wall to the outside Face wall face fig. 23 Flue terminal position Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Electrical connections 1.8.1 Mains connection NOTE All Boulter Buderus boilers require a permanent live. A mains supply of 230 V - 50Hz is required. External controls are suitable for volt free or 230 V installation. Wiring to the boiler MUST be in accordance with the current I.E.E.
24 VAC HW TANK SENSOR (Boulter Buderus prod.) RTH-CONVERTER OR MODULINK 250 RF Flow sensor Safety sensor Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 23
Boulter Buderus 24V controls; item 1, 2: Boulter Buderus control – a room-temperature control device at 230V connected to item 3, 4: Boulter Buderus cylinder valve the rth-converter (see subsection 1.10.4, S-plan and item: 5, 6, 7: Diverter valve Y-plan);...
Page 24
(fig. 28). fig. 28 Place receiver into bracket Remove the boiler's casing. fig. 29 Remove casing Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 25
DBA (see fig. 32, item 1). RTH- converter fig. 32 Room thermostat connection on DBA Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 26
Fix the wire to terminal 1 and 2 of the volt free connection (fig. 33, item 3). Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Installation 1.11 System examples NOTE Example systems are to be regarded as schematic representations only. Buderus 500-24S with ModuLink 250 RF or other Boulter Buderus controls Key to abbreviations: Cylinder AV = Air Vent BCT = Boulter Buderus cylinder thermostat...
Page 28
Gr/Yel Black lead JB 230 vac Boiler DBA fig. 36 Wiring diagram Y-plan with exernal 230V controls Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 29
Grey Orange Gr/Yel fig. 38 Wiring diagram S-plan with external 230V controls and two port zone valves Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Follow the steps described in this chapter to properly commis- sion the boiler and fill out the commissioning log book. NOTE If a fault occurs, then refer to the servicing manual or contact Boulter Buderus. Preparing the boiler for operation CAUTION DO NOT operate the condensing gas boiler if large amounts of dust are present, e.g.
Page 31
1.0 bar then top up the system as described previously. Disconnect the filling loop and cap off. Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 32
43 Disconnect hose from condensate trap fig. 44 Remove the condensate trap and fill with water Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 33
('Lo' appears in the display, fig. 47). fig. 47 DBA display Lo Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 34
When summer operation is active then the boiler will not operate for central heating until summer operation has been deactivated. Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 35
– measuring the working gas-supply pressure (boiler 3.45 Standard (LPG) operating at full power). table 3 Gas injector diameter Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 36
If the required connection pressure is incorrect item 1: Gas valve closed contact your gas supplier. item 2: Gas valve open Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 37
(see fig. 55). fig. 55 DBA with open-end spanner Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 38
The product must be certified as a gasleak- testing agent. Do not allow the product to come into contact with the electrical wiring. Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Page 39
Explain and demonstrate the lighting and shutting down procedures. NOTE Always keep the user manual and installation and servicing instructions available for feed- back. Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Check the pre-pressure of the expansion vessel 3.2.6 Check the hot water cylinder for leakage 3.2.7 Check the programming of the room thermostat Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Now the front cover of the heat exchanger can be removed by opening the latches (fig. 60, item 1). fig. 62 Remove gas air unit Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...
Undo the condensate drain connection (see fig. 64, item 1) and remove the syphon. Rinse and refit the syphon. fig. 65 Remove the condensate trap Subject to modifications resulting from technical improvements! Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk Installation and maintenance instructions for Buderus 500 - 24/S • 03/2005...