Working Limits - Mitsubishi Electric t-NEXT DF DX 011 P1 S Manual

Air conditioners for it cooling with dual fluid system.to be matched with remote air-cooled condenser.
Table of Contents

Advertisement

t-NEXT DF DX

WORKING LIMITS

T_tNEXTDFDX_0719_EN
ROOM AIR CONDITIONS
Room air temperature:
14°C
minimum temperature with wet bulb.
24°C
maximum temperature with wet bulb.
18°C
minimum temperature with dry bulb
40°C
maximum temperature with dry bulb.
AREA "A". Machine operating envelope.
Room air humidity:
20%RH
minimum relative humidity.
60%RH
maximum relative humidity.
AMBIENT AIR TEMPERATURE
45°C
Maximum ambient air temperature
-20°C
Minimum ambient air temperature
With "Kit for air -45°C" for low ambient temperature operation (optional)
-45°C
minimum ambient air temperature with remote condensers with AC fans
CHILLED WATER TEMPERATURE (Dual Fluid circuit)
6-25°C
temperature range of the water entering the coil
ΔT 3°C
Minimum temperature difference between water inlet and outlet
ΔT 10°C
Maximum temperature difference between water inlet and outlet
All the values are indicative. The working temperatures are influenced by a series of variables as:
Working conditions;
Thermal load;
Set of the microprocessor control.
HYDRAULIC CIRCUIT (Dual Fluid circuit)
ΔP 5-150kPa Pressure drop range of the hydraulic circuit.
10 Bar
Maximum working pressure of the hydraulic circuit
POWER SUPPLY
± 10%
Maximum tolerance of the supply voltage (V)
± 2%
Maximum unbalancing of the phases.
8
Relative humidity - %
A
Dry bulb temperature - °C
MEHITS S.p.A.
DATA BOOK