Connecting the water coil (W)
The installation must be carried out by an
authorised installer.
The water coil has copper tubes with
aluminium fins and is suitable for connection
to a closed water heating system. The heating
coil must not be connected to a mains
pressure water system or an open water
system.
Note that the unit shall be preceded by a
regulating valve, see Frico valve kit.
The water coil is connected on the side
of the unit via DN25 (1''), internal thread
connections.
Flexible hoses are available as an accessory,
see accessories pages.
NOTE: Care must be taken when connecting
the pipes. Use a wrench or similar to hold the
air curtain connections to prevent straining
of the pipes and subsequent water leakage
during connection to water supply pipe-work.
The connections to the heating coil must
be equipped with shut off valves (included
in Frico valve kits) to allow problem free
removal. A vent valve should be connected at a
high point in the pipe system. Air valves are not
included
Basic setting fan speed
The fan speed when the door is open is set
using the control. Note that the air flow
direction and fan speed may need fine
adjustment depending on the loading of the
door.
Filter (W)
The distance between the fins in combination
with the hole diameter of the intake grille
prevents the coil from clogging. This normally
makes a separate filter unnecessary.
Service, repairs and maintenance
For all service, repair and maintenance first
carry out the following:
1. Disconnect the power supply.
2. Service hatch is opened by removing the
screws on the top or bottom side of the
unit.
RDS
Maintenance
Unit with water heating:
The appliance filter should be cleaned
regularly to ensure the air curtain effect and
the heat emission from the device. How often
depends on local circumstances. A clogged
filter is not a risk, but the appliance function
can fail. Vacuum the intake grille regularly
from outside when dust is visible, for example
as a part of the cleaning routine.
All units:
Since fan motors and other components are
maintenance free, no maintenance other than
cleaning is necessary. The level of cleaning
can vary depending on local conditions.
Undertake cleaning at least twice a year. Inlet
and exhaust grilles, impeller and elements
can be vacuum cleaned or wiped using a
damp cloth. Use a brush when vacuuming
to prevent damaging sensitive parts. Avoid
the use of strong alkaline or acidic cleaning
agents.
Overheating
The air curtain unit with electric heater is
equipped with an overheat protector. The
overheat protection is reset by turning
off the switch and the unit cools. If it is de-
ployed due to overheating, reset as follows:
1. Disconnect the electricity with the fully
isolated switch.
2. Allow the electrical coil to cool.
3. Determine the cause of overheating and
rectify the fault.
4. Connect the air curtain again.
All motors are equipped with an integral ther-
mal safety cut-out. This will operate, stopping
the air curtain should the motor temperature
rise too high. The cut-out will automatically
reset when the motor temperature has retur-
ned to within the motor's operating limits.
Temperature control
Temperature control of SIRe maintains the
exhaust temperature. If the temperature
should exceed there is an overheating alarm.
For more information see the manual for
SIRe.