Percentage - andrews ECOflo Series Installation And Service Manual

High efficiency condensing storage water heaters for natural gas and propane
Table of Contents

Advertisement

4
Commissioning
4.4
CO² Percentage (Natural Gas)
Model Reference
EC230/600
EC230/700
EC230/960
EC380/740
EC380/980
EC380/1220
EC380/1400
EC380/1900
CO² Percentage (LPG)
Model Reference
EC230/600
EC230/700
EC230/960
EC380/740
EC380/980
EC380/1200
EC380/1400
EC380/1900
44
Input rating
Combustion
kW/hr
CO
/CO
2
36.6
11.0%/10 ppm
43.9
10.3%/20 ppm
58.6
9.7%/10 ppm
43.9
10.4%/15 ppm
58.6
9.8%/15 ppm
73.2
10.6%/15 ppm
85
11.0%/15 ppm
118.7
11.0%/15 ppm
Input rating
Combustion
kW/hr
CO
/CO
2
36.6
11.2%/11.5 ppm
43.9
10.5%/21 ppm
58.6
9.9%/11.5 ppm
43.9
10.5%/16.5 ppm
58.6
9.9%/16.5 ppm
73.2
10.8%/16.5 ppm
85
11.2%/16.5 ppm
118.7
11.2%/16.5 ppm
Flue Gas Volume
Vent Temperature
Cubic metres/hr
40
49
63
49
63
75
86
117
Flue Gas Volume
Flue Temperature
Cubic metres/hr
40
49
63
49
63
75
86
117
°C
50 – 60
50 – 60
55 – 60
45 – 50
50 – 55
50 – 60
55 – 60
55 – 60
°C
50 – 60
50 – 60
55 – 60
45 – 50
50 – 55
50 – 60
55 – 60
55 – 60
Issue 2 14/07/16