Agilent Technologies 3070 Series Site Preparation page 301

Board test systems site preparation
Hide thumbs Also See for 3070 Series:
Table of Contents

Advertisement

Chapter 10: Site Preparation – Power Requirements for Older Systems: Tester Power Requirements (Series I/II)
© Agilent Technologies 1989–2002
Table 10-37 2-phase open delta with center tap of one phase (05A)
System Type
327X
Breaker Size in Amps
20
SO Cord Conductor Size mm2 (American Wire Gauge - AWG)
4 (12)
Table 10-38 Single-phase wye w/neutral (05B, 05G, 05K)
System Type
327X
Breaker Size in Amps
30
SO Cord Conductor Size mm2 (American Wire Gauge - AWG)
4 (12)
Agilent 3070 / 79000 Site Preparation
317X
30
6 (10)
317X
40
6 (10)
307X
50
10 (8)
307X
70
6 (10)
10-140

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

79000 series

Table of Contents