Chapter 10: Site Preparation – Power Requirements for Older Systems: Series 3 Power Requirements and Connections (Prior to May 2000)
Table 10-9 Series 3 and 79000 family power requirements (single-phase power)
E1135C
Power
Option
Single-Phase Wye w/
AWV
Neutral
L1
L2
AWZ
05B
05G
N
G
05K
Single-Phase Earthed
05M
05F
L1
05J
N
G
© Agilent Technologies 1989–2002
Voltage
Full-Load Amps (FLA)
327X / 79000
5
120 /
[25]
20
208
127 /
[25] 20
220
220 /
[18] 11
380
230 /
[18] 11
400
240 /
[18] 11
415
220
[22] 20
230
[22] 20
240
[22] 20
Agilent 3070 / 79000 Site Preparation
1
2
for:
3
317X
307X
Testhead
[43] 24
[42] 28
[43] 24
[42] 28
[21] 12
[37] 22
[21] 12
[37] 22
[21] 12
[37] 22
[36] 24
[42] 28
[36] 24
[42] 28
[36] 24
[42] 28
xDSL/POTS
4
Bay
Support Bay
Opts/Current
[24] 15
AWY, 16
[24] 15
AWZ, 16
NA
05M, 14
NA
05F, 14
NA
05J, 14
[24] 15
14
[24] 15
14
[24] 15
14
10-86