Chapter 10: Site Preparation – Power Requirements for Older Systems: Series 3 Power Requirements and Connections (Prior to May 2000)
© Agilent Technologies 1989–2002
Table 10-14 3-phase delta (0ED, 05C, 05H, 0E6)
System Type
327X / 79000
1
Breaker Size in Amps
[20] 20
Wire Size mm2 (American Wire Gauge - AWG)
[4 (12)] 4(12)**
1. Breaker size based on 125 percent of maximum rms current
2. Wire size based on multiconductor cables
* Three current-carrying conductors
** Four current-carrying conductors
*** Pigtail required (Appendix 10,
Pigtail to the E1135C PDU
.)
Agilent 3070 / 79000 Site Preparation
317X
[30] 30
2
[10(8)] 6(10)*
Connecting a
307X
[60] 35
[25 (4)]*** 6(10)