11.8 Condensate drain

5
1
1
Condensate drain or
2
Drain pan connected to drain
3
T&P valve
4
Cold water connection
5
Hot water connection
6
Condensate spillover
The condensate drain is located on the side of the water heater.
This is where you can connect a drain hose.
When installing the unit outdoors, the condensate can drain off
freely.
For indoor installation, the condensate can be routed into a floor
drain or routed through the wall up to 889 mm (35") (see diagram
above).
If required, install a condensate pump.
To ensure the condensate drains correctly, never kink
the hose.
WWW.STIEBEL-ELTRON-USA.COM

11.9 Water connection

The water connection must be carried out by a qualified licensed
plumber.
The cold water connection must comply with DIN 1988 [or state
6
and local codes]
» Prior to installing the water heater, flush the line thoroughly.
3
3
C
H
M
12
4
2
1
Vacuum breaker
2
Hot water connection (Union adaptor to 3/4")
3
Mixing valve (optional, supplied by installer)
Connection for T&P valve ¾"
4
T&P valve ¾", 0.69 MPa @99 °C (100 psi @210 °F) (supplied
5
with unit)
6
0.551 MPa (80 psi) relief valve (optional, supplied by
installer)
7
Expansion tank (optional, supplied by installer)
8
Straight-through shut-off valve (supplied by installer)
9
Check valve (optional, supplied by installer)
10 0.48 MPa (70 psi) pressure reduction valve (optional,
supplied by installer)
11 Cold water connection (with Union adaptor to 3/4")
12 Condensate drain (elbow supplied with unit)
13 Drain valve (supplied by installer)
14 Drain pan (supplied by installer)
15 Condensate spillover
» Remove the protective plastic caps from the connectors.
» Connect the plumbing.
Risk of damage through corrosion
To protect against the risk of corrosion, make the
connection with flat gaskets.
» Insulate the hot water line against heat loss.
» Install a drain valve at the lowest point of the cold water
supply.
Install a 0.48 MPa (70 psi) pressure reducing valve on the cold
water inlet.