Menu Operation; Setpoint Setting; Setting Of Operating Mode; Fault Indications - Grundfos LME Series Installation And Operating Instructions Manual

Table of Contents

Advertisement

5.1 Menu
OPERATION
When communication between the R100 and the pump has been
established, the first display in this menu will appear.

5.1.1 Setpoint setting

Setpoint set
Actual setpoint
Actual value
In this display, the setpoint is set.
In controlled-operation mode, the setting range is equal to the
sensor measuring range, e.g. 0 to 25 m.
In uncontrolled-operation mode, the setpoint is set in % of the
maximum performance. The setting range will lie between the
min. and max. curves.
Select one of the following operating modes:
Stop,
Min. (min. curve),
Max. (max. curve).
If the pump is connected to an external setpoint signal, the set-
point in this display will be the maximum value of the external set-
point signal, see section 7. External setpoint signal.
If the pump is controlled via external signals (Stop, Min. curve or
Max. curve) or a bus, this will be indicated in the display if set-
point setting is attempted.
In this case, the number of possible settings will be reduced, see
section 9. Priority of settings.

5.1.2 Setting of operating mode

Select one of the following operating modes:
Stop,
Min.,
Normal (duty),
Max.
The operating modes can be selected without changing the set-
point setting.

5.1.3 Fault indications

If the pump is faulty, the cause will appear in this display.
Possible causes:
Too high motor temperature
Undervoltage
Overvoltage
Phase failure (three-phase pumps only)
Mains supply failure (three-phase pumps only)
Too many restarts (after faults)
Overload
Sensor signal outside signal range (only 4-20 mA)
Setpoint signal outside signal range (only 4-20 mA)
Dry running
Other fault
A fault indication can be reset in this display if the cause of the
fault has disappeared.

5.1.4 Alarm log

If faults have been indicated, the last five fault indications will ap-
pear in the alarm log. "Alarm log 1" shows the newest/latest fault.
The example shows the fault indication "Undervoltage", the fault
code and the number of minutes the pump has been connected to
the electricity supply after the fault occurred.
The time cannot be displayed for three-phase pumps as the soft-
ware does not support this function.

5.2 Menu STATUS

The displays appearing in this menu are status displays only. It is
not possible to change or set values.
The displayed values are the values that applied when the last
communication between the pump and the R100 took place. If a
status value is to be updated, point the R100 at the control panel
and press "OK".
If a parameter, e.g. speed, should be called up continuously,
press "OK" constantly during the period in which the parameter in
question should be monitored.
The tolerance of the displayed value is stated under each display.
The tolerances are stated as a guide in % of the maximum values
of the parameters.

5.2.1 Display of actual setpoint

Tolerance: ±2%
This display shows the actual setpoint and the external setpoint in
% of the range from minimum value to the setpoint set, see sec-
tion 7. External setpoint signal.

5.2.2 Display of operating mode

This display shows the actual operating mode (Stop, Min., Normal
(duty) or Max.). Furthermore, it shows where this operating mode
was selected (R100, Pump, BUS or External).

5.2.3 Display of actual value

The actually measured value of a connected sensor will appear in
this display, e.g. 12 metres.
If no sensor is connected to the pump, "–" will appear in the dis-
play.
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents