Troubleshooting; Diagnosing Errors; Error Codes - Honeywell 2MLF-DV4S User Manual

Isolated analog output module
Table of Contents

Advertisement

7.1

Diagnosing errors

Error codes

The following table describes the details and diagnosis of errors which occur while D/A
conversion module.
Error Code
(Dec)
10
11
12
13
21
31
32
40
41#
50#
51#
52#
R200
Isolated Analog Output Module 2MLF-DV4S, 2MLF-DC4S User's Guide
September 2010

7. Troubleshooting

Module error (Reset Check Error)
Module error (RAM Check Error)
Module error (Register Check Error)
2
Module error (E
PROM Check Error)
Module error (D/A Conversion Error)
Parameters setting error of current module. Refer to Attention.
Parameters setting error of current module when setting
Offset/Gain. Refer to Attention.
Setting error of current module's digital input range (If input value is
set less than -192 or greater than 16191). The range changes
based on input data type. Refer to Attention.
Setting error of voltage module's digital input range (If input value is
set less than -192 or greater than 16191). The range changes
based on input data type. Refer to Attention.
Offset/Gain setting error in current module of 4~20mA
(Offset value is set greater than or equal to Gain value). Refer to
Attention.
Offset/Gain setting error in current module of 0~20mA
(Offset value is set greater than or equal to Gain value). Refer to
Attention.
Offset/Gain setting error in voltage module of 1~5V. Refer to
Attention.
(Offset value is set greater than or equal to Gain value)
Honeywell
Description
LED
status
Blinks
every
0.2s.
Blinks
every
1s.