Error Code
(Dec)
41#
50#
51#
52#
53#
54#
55#
R200
Isolated Analog Output Module 2MLF-DV4S, 2MLF-DC4S User's Guide
September 2010
Description
(If input value is set less than -192, or greater than
16191)
The range changes based on input type. Refer to
Attention.
Setting error of voltage module's digital input range
(If input value is set less than -192, or greater than
16191)
The range changes based on input type. Refer to
Attention.
Offset/Gain setting error in current module of 4~20mA
(If Offset value is set greater than or equal to Gain
value). Refer to Attention.
Offset/Gain setting error in current module of 0~20mA
(If Offset value is set greater than or equal to Gain
value). Refer to Attention.
Offset/Gain setting error in voltage module of 1~5V
(If Offset value is set greater than or equal to Gain
value). Refer to Attention.
Offset/Gain setting error in voltage module of 0~5V
(If Offset value is set greater than or equal to Gain
value). Refer to Attention.
Offset/Gain setting error in voltage module of 0~10V
(If Offset value is set greater than or equal to Gain
value). Refer to Attention.
Offset/Gain setting error in voltage module of -10~10V
(#: channel)
(If Offset value is set greater than or equal to Gain
value). Refer to Attention.
Honeywell
5. Internal Memory Configuration
5.3. Operation parameters settings
LED status