Switch point adjustment (only possible on VEGAMET 308)
• Set A/B-switch acc. to the following description to the desired mode
A or B.
Mode A
When exceeding the adjusted max. level:
Relay de-energized
Relay control lamp lights
Terminals 9-10 are connected through relay
Mode B
When decreasing the adjusted min. level:
Relay de-energized
Relay control lamp lights
Terminals 9-10 are connected through relay
• Adjust switch point for min. level
Push button for adjustment of the min. switch point and adjust the
potentiometer of
the indicating instrument to the desired min. value.
• Adjust switch point for max. level
Push button for adjustment of the max. switch point and adjust the
potentiometer
of the indicating instrument to the desired max. value.
Adjustment for single-point switching
• Push button for adjustment of the max. switch point and set the
indicating instrument
with the respective potentiometer to "0".
• Push button for adjustment of the min. switch point and set the
indicating instrument
with the respective potentiometer to the required value.
Note:
The switching hysteresis is in this case 0,5 %.
HiTECH Technologies, Inc.
301 Oxford Valley Road - Building 505
Yardley, PA 19067-7706
Tel: 215. 321. 6012; Fax: 215. 321. 6067
Tech Support (Toll Free) 866-DrLevel or 888-NIVELCO
Email: info@DrLevel.com or info@hitechtech.com
Web Site: www.DrLevel.com or
www.hitechtech.com

Advertisement

loading

This manual is also suitable for:

Vegamet 307