Siemens SIPLUS CMS4000 Operating Instructions Manual

Media converter node

Advertisement

Operating Instructions SIPLUS CMS4000 MCN11
Media Converter Node (MCN11)
6AT8000-1EB00-3XA0
Operating Instructions - English
Release 2017-06
SIPLUS CMS4000 MCN11
Operating Instructions, 06/2017, A5E02298098A-AA
1
2
3
4
5
6
7
1

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIPLUS CMS4000

  • Page 1: Table Of Contents

    Operating Instructions SIPLUS CMS4000 MCN11 Preface Product Overview SIPLUS CMS4000 Installation Media Converter Node (MCN11) Wiring 6AT8000-1EB00-3XA0 Commissioning and Diagnosis Technical Data Appendix Operating Instructions - English Release 2017-06 SIPLUS CMS4000 MCN11 Operating Instructions, 06/2017, A5E02298098A-AA...
  • Page 2: Siplus Cms4000

    Siemens. Trademarks All designations marked with ® are registered trademarks of Siemens AG. Other designations in this documentation might be trade- marks which, if used by third parties for their purposes, might infringe upon the rights of the proprietors.
  • Page 3 Operating Instructions SIPLUS CMS4000 MCN11 Table of Contents Preface..........................5 Purpose of the Operating Instructions..............5 Required Basic Knowledge ..................5 Validity of this Document ..................5 Modification compared with the Previous Version ...........5 CE Marking ......................5 Standards ......................5 Directory ........................6 Recycling and Disposal ..................6 Product Overview ........................7...
  • Page 4 Operating Instructions SIPLUS CMS4000 MCN11 Appendix ........................... 30 Order Numbers ....................30 Dimensional Drawing ................... 31 Service & Support on the Internet ................. 32 List of Abbreviations ..................... 32 SIPLUS CMS4000 MCN11 Operating Instructions, 06/2017, A5E02298098A-AA...
  • Page 5: Preface

    Operating Instructions SIPLUS CMS4000 MCN11 Preface Purpose of the Operating Instructions This operating instructions supports you to operate the Media Converter Node SIPLUS CMS4000 MCN11, named MCN11 as peripheral device in the System SIPLUS CMS4000. Required Basic Knowledge Basic knowledge of automation technology and equipment condition monitoring is nec- essary.
  • Page 6: Directory

    Operating Instructions SIPLUS CMS4000 MCN11 Directory The operating instructions describe the hardware of the Media Converter Node MCN11. It contains the following topics: · Installation and wiring (Chapter 3 and 4) · Commissioning and diagnosis (Chapter 5) · Order Numbers (Chapter 7) ·...
  • Page 7: Product Overview

    Operating Instructions SIPLUS CMS4000 MCN11 Product Overview What is SIPLUS CMS? SIPLUS CMS is an industrial-suited Condition Monitoring System for technical and tech- nological services in industrial plants. SIPLUS CMS is a modular, scalable analysis and diagnosis system. It is optimized for reaction less measurement of analog, binary and numerical data.
  • Page 8: What Is A Media Converter Node (Mcn11)

    Operating Instructions SIPLUS CMS4000 MCN11 What is a Media Converter Node (MCN11)? Definition The MCN11 transforms the transmitting data at physical layer from one medium (electri- cal) to another medium (optical) and vice versa. MCN11 is used for the communication, when the linking length is longer than 4.5 meters.
  • Page 9: Scope Of Delivery

    Operating Instructions SIPLUS CMS4000 MCN11 Scope of Delivery · Device MCN11 - incl. clamp for DIN Rail mounting - LWL Cable entry for LWL twin connectors (other LWL Types on request) · Operating Instructions (compact) Unpacking and Checking After unpacking, please check ·...
  • Page 10: Installation

    Operating Instructions SIPLUS CMS4000 MCN11 Installation Installation Position, Dimensions Installation Position The MCN11 is suited for installation on a DIN rail or for attachment with mounting angles. Dimension and Expansion Spaces Chart 1 Dimensions with and without DIN rail/mounting angles...
  • Page 11: Din Rail

    Operating Instructions SIPLUS CMS4000 MCN11 DIN Rail Characteristics The device can be installed on a DIN rail. 3.2.1 Installation Requirements The table-track is installed on the device. Procedure Hang the upper table-track of the device on the DIN rail and push it down towards the DIN rail so that it snaps in.
  • Page 12: Disassembling

    Operating Instructions SIPLUS CMS4000 MCN11 3.2.2 Disassembling Procedure Make sure that all electronic connection cables are dissembled professionally. Remove the device from the DIN rail: Push the device down against the DIN rail and hang it out. Picture 5 Disassembly of the MCN11 from the DIN rail...
  • Page 13: Mounting Angle

    Operating Instructions SIPLUS CMS4000 MCN11 Mounting Angle Characteristics The device will be installed with mounting angles on a stable base (e.g. wall, mounting plate). 3.3.1 Installation Requirements The „MCN11 Mounting Set“ is necessary for the installation with mounting angles. In the „MCN11 Mounting Set“ is a drill template included in the equipment pack.
  • Page 14: Label Plate

    Operating Instructions SIPLUS CMS4000 MCN11 Label Plate Characteristics You can mark the device with a label plate. The label plate is exchangeable. Exchanging the label plate 1. Push the screwdriver in the small opening on the bottom edge of the label plate and hang it out.
  • Page 15: Wiring

    Operating Instructions SIPLUS CMS4000 MCN11 Wiring General Rules and Regulations for operation of MCN11 Protection against external electrical influences The following chart shows what you have to observe for the protection of electrical influ- ences or faults. Chart 2 Protection against external electrical influences At…...
  • Page 16: Mcn11

    Operating Instructions SIPLUS CMS4000 MCN11 MCN11 4.2.1 Connecting optical fiber cable (LWL) 1. Open the 4 screws on the device with an Allen key (SW3). Picture 8 Open all 4 screws 2. Release only the screwcap of the screw connection (PG-screwing) and pull the „SC/PC-plug“...
  • Page 17 Operating Instructions SIPLUS CMS4000 MCN11 4. Insert the „SC/PC-plug“ of the LWL-single connectors separately through the cable entry in the box. Case screw (4x) Sealing insert Screwcap SC/PC-plug Cable entry Picture 10 LWL-cable entry configuration 5. Connecting „SC/PC-Plugs“. Device 1 Device 2 ▼▲...
  • Page 18 Operating Instructions SIPLUS CMS4000 MCN11 6. Slide the sealing insert flush in the cable entry so that the LWL-single connector lays parallel in the box (in order to avoid a mechanical overload of LWL). 7. Screw and tighten the screwcap on to the cable entry. Recommended tightening...
  • Page 19: Connecting Mcn11 To The Ground (Shield)

    Operating Instructions SIPLUS CMS4000 MCN11 4.2.2 Connecting MCN11 to the ground (SHIELD) The earth connection has to be implemented with cable cross section of 2,5mm 1. Isolate the grounding cable and squeeze a cable lug at the end of the line (M4 ring eye).
  • Page 20: Ieee1394 Interface (Lnk)

    Operating Instructions SIPLUS CMS4000 MCN11 4.2.3 IEEE1394 Interface (LNK) Connect the M12 connector on the front side of the box in the 8-pin socket plug (LNK). For this purpose use the cable with the order number (MLFB) 6AT8000-2AB20-2AA2. Caution Using standard SIPLUS CMS cables is necessary. In case of using self-made cable connection there is no warranty assumed.
  • Page 21 Operating Instructions SIPLUS CMS4000 MCN11 2. Twist the M12-socket plug with the knurled ring nut tight until it snaps. (about 1/2 rota- tion). Picture 15 M12-socket plug interlocking 3. The end position (interlock) of the M12-socket plug is now finished.
  • Page 22: Cable Information

    Operating Instructions SIPLUS CMS4000 MCN11 4.2.4 Cable Information Depending on the LWL cable an adequate sealing insert is needed. The integrated seal- ing is suitable for LWL cable with 3mm diameter. Caution The laying information of the LWL-cable manufacturer has to be observed.
  • Page 23: Commissioning And Diagnosis

    Operating Instructions SIPLUS CMS4000 MCN11 Commissioning and Diagnosis Commissioning and Start-up of MCN11 Caution Plugging and pulling between the electrical connection between MCN11 and IFN is acceptable with voltage and without voltage. Notice that the life-time of the cable and MCN11 reduces, when pulling and plugging with voltage.
  • Page 24 Operating Instructions SIPLUS CMS4000 MCN11 PC / SIPLUS CMS Microbox Multi-Port-Repeater (RPN IEEE1394B T001/T002) RPN/PC-Cable Media Converter Node (MCN11) IFN/MCN-Cable Picture 18 Example of the connection configuration between PC and CMS4000 System SIPLUS CMS4000 MCN11 Operating Instructions, 06/2017, A5E02298098A-AA...
  • Page 25: Requirements For Commissioning

    Operating Instructions SIPLUS CMS4000 MCN11 5.1.1 Requirements for Commissioning 1. MCN11 mounted (view chapter 3). 2. MCN11 wired (view chapter 4). 5.1.2 Commissioning of MCN11 Picture 19 Start-up of MCN11 Diagnosis via LED-indicators Name Description power indicator Color green Condition...
  • Page 26: Technical Data

    Operating Instructions SIPLUS CMS4000 MCN11 Technical Data Standards and Approvals Product Name Device SIPLUS CMS4000 MCN11 EMV Directive The product is designed for use in industrial environment. Area of Application Requirements for Emission Immunity Industry DIN EN 55011:2007 Group 1, class A...
  • Page 27 Operating Instructions SIPLUS CMS4000 MCN11 Notes for the manufactures of machines This product is not a machine in the sense of the EC Machinery Directive. There is therefore no declaration of conformity relating to the EC Machinery Directive 89/392/ECC for this product.
  • Page 28: Technical Data

    Operating Instructions SIPLUS CMS4000 MCN11 Technical Data Interfaces and connections IEEE 1394a electrical Number Connector type 8-pin receptacle connector (M12) Transfer speed 400 Mbps Applicable cable Tailor made 8-pin cable with shield (length: 30 cm) (connection: IFN to MCN11) MLFB: 6AT8000-2AB20-2AA2 Power input MCN11 ca.
  • Page 29: Approval

    Operating Instructions SIPLUS CMS4000 MCN11 Approval Chart 3 Approval Approval Mark Declaration of conformity ATEX approval II 3G Ex nA IIC T4 Gc DEK 14 ATEX 0084 X IECEx approval IECEx DEK 14.0040 X EAC certification KC certification RCM certification...
  • Page 30: Appendix

    SIPLUS CMS „MCN Mounting Set“ for installation with 6AT8000-2BB00-0XC0 mounting angle incl. drill template Cable IEEE1394 IFN/MCN cable Length 30 cm 6AT8000-2AB20-2AA2 Further information is available from your local Siemens office and from the homepage www.siemens.com/siplus-cms. SIPLUS CMS4000 MCN11 Operating Instructions, 06/2017, A5E02298098A-AA...
  • Page 31: Dimensional Drawing

    Operating Instructions SIPLUS CMS4000 MCN11 Dimensional Drawing SIPLUS CMS4000 MCN11 Operating Instructions, 06/2017, A5E02298098A-AA...
  • Page 32: Service & Support On The Internet

    Operating Instructions SIPLUS CMS4000 MCN11 Service & Support on the Internet In addition to our documentation pool we offer our complete knowledge base on the In- ternet: www.siemens.com/automation/service&support There you find: · The newsletter, which is constantly updated to provide you with the latest information about your products.

This manual is also suitable for:

Mcn11

Table of Contents