Advertisement

Quick Links

Operating Instructions SIPLUS CMS4000 IFN AI-D
Interface Node
IFN ANALOGINPUT-DISTANCE (IFN AI-D)
6AT8000-1BB00-2XA0
Operating Instructions - English
Release 2021-07
SIPLUS CMS4000 IFN AI-D
Operating Instructions, 07/2021, A5E32612781A-AB
Technical Data
Appendix
1
2
3
4
5
6
7
1

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIPLUS CMS4000

  • Page 1: Table Of Contents

    Operating Instructions SIPLUS CMS4000 IFN AI-D Preface Product Overview SIPLUS CMS4000 Installation Interface Node IFN ANALOGINPUT-DISTANCE (IFN AI-D) Wiring 6AT8000-1BB00-2XA0 Commissioning and Diagnosis Technical Data Appendix Operating Instructions - English Release 2021-07 SIPLUS CMS4000 IFN AI-D Operating Instructions, 07/2021, A5E32612781A-AB...
  • Page 2 Siemens. Trademarks All designations marked with ® are registered trademarks of Siemens AG. Other designations in this documentation might be trade- marks which, if used by third parties for their purposes, might infringe upon the rights of the proprietors.
  • Page 3 Operating Instructions SIPLUS CMS4000 IFN AI-D Table of Contents Preface..........................5 Purpose of this Document ..................5 Required Basic Knowledge ..................5 Validity of this Document ..................5 Modification compared with the Previous Version ...........5 CE Marking ......................5 Standards ......................5 Classification of Information ...................5 Directory ........................6...
  • Page 4 Operating Instructions SIPLUS CMS4000 IFN AI-D Mixed configurations with ION and IFN ..............25 Technical Data ........................27 Standards and Approvals ..................27 Technical Specification..................29 6.2.1 Communication (LNK0…LNK2) ................29 6.2.2 Power Supply (PWR) ................... 29 6.2.3 Analog Input (CH1…CH6) ..................30 6.2.4...
  • Page 5: Siplus Cms4000

    Operating Instructions SIPLUS CMS4000 IFN AI-D Preface Purpose of this Document This operating instructions support you to operate the Media Converter Node SIPLUS CMS4000 IFN ANALOGINPUT-DISTANCE, named IFN AI-D as peripheral device in the System SIPLUS CMS4000. Required Basic Knowledge Basic knowledge of automation technology and equipment condition monitoring is nec- essary.
  • Page 6: Directory

    Operating Instructions SIPLUS CMS4000 IFN AI-D Directory The operating instructions describe the hardware of the Interface Node IFN AI-D. It contains the following topics:  Installation and wiring (Chapter 3 and 4)  Commissioning and diagnosis (Chapter 5)  Order numbers (Chapter 7) ...
  • Page 7: Product Overview

    Operating Instructions SIPLUS CMS4000 IFN AI-D Product Overview What is SIPLUS CMS? SIPLUS CMS is an industrial-suited Condition Monitoring System for technical and tech- nological services in industrial plants. SIPLUS CMS is a modular, scalable analysis and diagnosis system. It is optimized for reaction less measurement of analog, binary and numerical data.
  • Page 8: What Is An Interface Node Ifn Ai-D

    Operating Instructions SIPLUS CMS4000 IFN AI-D What is an Interface Node IFN AI-D? Definition The interface node IFN AI-D allows the data sampling of six analog signals. The maximum sampling frequency is 192 kHz per channel. The nodes are connected via bus system (IEEE1394) with 400 Mbps with an industrial PC.
  • Page 9: Scope Of Delivery

    Operating Instructions SIPLUS CMS4000 IFN AI-D Scope of Delivery What is delivered?  Device IFN AI-D (incl. clamp for DIN Rail mounting)  Operating Instructions (compact) Unpacking and Checking After unpacking, please check  the packet for completeness and  all parts for transport damages.
  • Page 10: Installation

    Operating Instructions SIPLUS CMS4000 IFN AI-D Installation Installation Position, Dimensions Installation Position The interface node IFN AI-D is suited for installation on a DIN Rail or for attachment with mounting angles. Dimensions and Expansion Spaces Chart 1 Dimensions Dimensions with DIN rail...
  • Page 11: Din Rail

    Operating Instructions SIPLUS CMS4000 IFN AI-D DIN Rail Characteristics The Device can be installed on a DIN rail (DIN EN 60715 TH35-15). 3.2.1 Installation Requirements The table-track is installed on the device. Procedure Hang the upper table-track of the device on the DIN rail and push it down towards the DIN rail so that it snaps in.
  • Page 12: Disassembling

    Operating Instructions SIPLUS CMS4000 IFN AI-D 3.2.2 Disassembling Procedure Dissemble all electronic connection cables. Remove the device from the DIN rail: Push the device down against the DIN rail and hang it out. Picture 5 Disassembly of the IFN AI-D from the DIN rail...
  • Page 13: Mounting Angles

    Operating Instructions SIPLUS CMS4000 IFN AI-D Mounting Angles Characteristics The device will be installed with mounting angles on a stable base (e.g. wall, mounting plate). 3.3.1 Installation Procedure The „IFN Mounting Set“ is necessary for the installation with mounting angles.
  • Page 14: Label Plate

    Operating Instructions SIPLUS CMS4000 IFN AI-D Label Plate Characteristics You can mark the device with a label plate. The label plate is exchangeable. Exchanging the label plate 1. Push the screwdriver in the small opening on the bottom edge of the label plate and hang it out.
  • Page 15: Wiring

    Operating Instructions SIPLUS CMS4000 IFN AI-D Wiring General Rules and Regulations for operation of IFN AI-D DC 24V-Supply The following chart shows what you have to observe for the DC 24 V-Supply. Chart 2 DC 24V-Supply At… you must ensure that …...
  • Page 16: Ifn Ai-D

    Operating Instructions SIPLUS CMS4000 IFN AI-D IFN AI-D 4.2.1 Connecting IFN AI-D to the ground (SHIELD) The earth connection has to be implemented with cable cross section of 2.5mm 1. Isolate the grounding cable and squeeze a cable lug at the end of the line (M4 ring eye).
  • Page 17: Connecting M12-Plugs

    Operating Instructions SIPLUS CMS4000 IFN AI-D 4.2.2 Connecting M12-plugs Caution The pictures 9, 10 and 11 shall only explain the concept of the plug type. The principle operation stays the same. 1. Push the M12 connector in vertical position in the socket plug, so that the slot from the connector and knurled ring nut are superposed.
  • Page 18 Operating Instructions SIPLUS CMS4000 IFN AI-D 3. The end position (interlock) of the M12-socket plug is now finished. Picture 11 Correct M12-socket plug connection Caution Avoid canting between M12 connector and socket plug! Only when the installation is correct, the protection category IP67 and safe contacting is guaranteed.
  • Page 19: Ieee1394 - Connection (Lnk)

    The product SIPLUS CMS4000 MCN11 is available for fiber optical cable coupling for distances over 4.5 m. Caution When using fiber optical cable coupling, the manual SIPLUS CMS4000 MCN11 is additionally needed! SIPLUS CMS4000 IFN AI-D Operating Instructions, 07/2021, A5E32612781A-AB...
  • Page 20: Power Supply Connection (Pwr)

    Operating Instructions SIPLUS CMS4000 IFN AI-D 4.2.4 Power Supply Connection (PWR) The power supply is connected to the 5-pin circular plug M12 (PWR) on the front side of the device. Y-Connector The Y-Connector enables looping of the 24V DC power supply and it is designed for maximum current load of 4A.
  • Page 21: Analog Input Channel

    Operating Instructions SIPLUS CMS4000 IFN AI-D 4.2.5 Analog Input Channel Connect the sensors / process signals to the 5-pin circular plug M12 (CH1-CH6) on the front side of the device. Chart 7 Channel 1-6, see chapter 6.2 Analog Input 1...
  • Page 22: Cable Traction Relief

    Operating Instructions SIPLUS CMS4000 IFN AI-D 4.2.6 Cable Traction Relief Caution You have to prepare adequate cable traction relief! 4.2.7 Sealing of not used round connectors Seal all not used round connectors with M12 end caps, in order to reach the degree of protection IP 67.
  • Page 23: Commissioning And Diagnosis

    Operating Instructions SIPLUS CMS4000 IFN AI-D Commissioning and Diagnosis Commissioning and Start-up of IFN AI-D 5.1.1 Software Requirements Tabelle 9 Software requirements for the commissioning Eingesetzte Projektierungssoftware Version SIPLUS CMS X-Tools starting version 4.00 and higher 5.1.2 Requirements for Commissioning 1.
  • Page 24: Uik (Unique Identification Key)

    Operating Instructions SIPLUS CMS4000 IFN AI-D 5.1.4 UIK (Unique Identification Key) The UIK is a clear, device dedicated identification/address. It is printed on the UIK label plate and deposited in the firmware of the IFN AI-D. The device is addressed with the UIK.
  • Page 25: Parameterization Of Ifn Ai-D

    Operating Instructions SIPLUS CMS4000 IFN AI-D Parameterization of IFN AI-D The IFN AI-D is parameterized through X-Tools. You will find parameterization details in the „SIPLUS CMS X-Tools Reference Manual”. Diagnosis through X-Tools You will find detailed information in the „SIPLUS CMS X-Tools Reference Manual”...
  • Page 26 Operating Instructions SIPLUS CMS4000 IFN AI-D PC/104-card Port2 PC/104-card Port3 plug 2 plug 1 PC/104-card PC/104- CMB IEEE1394A T011 Picture 14 MICROBOX PC with CMB IEEE1394A SIPLUS CMS4000 IFN AI-D Operating Instructions, 07/2021, A5E32612781A-AB...
  • Page 27: Technical Data

    Operating Instructions SIPLUS CMS4000 IFN AI-D Technical Data Standards and Approvals Product Name Device SIPLUS CMS4000 IFN AI-D EMV Directive The product is designed for use in an industrial environment. Area of Application Requirements for Emission Immunity Industry DIN EN 55011:2007 Gruppe 1, Klasse A...
  • Page 28 Operating Instructions SIPLUS CMS4000 IFN AI-D Notes for the manufactures of machines This product is not a machine in the sense of the EC Machinery Directive. There is therefore no declaration of conformity relating to the EC Machinery Directive 89/392/ECC for this product.
  • Page 29: Technical Specification

    Operating Instructions SIPLUS CMS4000 IFN AI-D Technical Specification 6.2.1 Communication (LNK0…LNK2) Chart 10 communication (LNK0…LNK2) Communication Parameter min. typ. max. Unit Connector three connectors (female) 8-pin (M12) Data protocol IEEE1394a / b Data transfer rate Mbps Galvanic isolation Lines to main electronic 6.2.2...
  • Page 30: Analog Input (Ch1

    Operating Instructions SIPLUS CMS4000 IFN AI-D 6.2.3 Analog Input (CH1…CH6) Chart 12 Analog input 1 to 6 (CH1…CH6) Specifications at TA=25ºC; Test conditions U = 24V DC (rated Voltage); unless otherwise noted; not allowed; overshoot is leading to demolition; Analog input Parameter min.
  • Page 31: Filter Characteristic Channel (Ch1

    Operating Instructions SIPLUS CMS4000 IFN AI-D 6.2.4 Filter Characteristic Channel (CH1…CH6) A m p litu d e / fre q u e n c y c h a ra c te ris tic " IF N A I" f(H z );...
  • Page 32: Input Impedance Channel (Ch1

    Operating Instructions SIPLUS CMS4000 IFN AI-D 6.2.5 Input Impedance Channel (CH1…CH6) Input impedance channel (CH1…CH6) Z (Ω) 1000000 100000 Z f(f); 10000 1000 1,E+00 1,E+01 1,E+02 1,E+03 1,E+04 1,E+05 f (Hz) Picture 16 Input impedance channel (CH1…CH6) of an IFN AI-D 6.2.6...
  • Page 33: Construction Assembly

    Operating Instructions SIPLUS CMS4000 IFN AI-D 6.2.8 Construction assembly Chart 15 Construction assembly Construction assembly Case Aluminum Dimensions with plug 210 x 86 x 87 (without mounting) (H x W x D) in mm 210 x 86 x 96 (DIN rail mounting)
  • Page 34: Appendix

    Length 200 cm – 6/6pole 6AT8000-2AA00-1AC0 Length 450 cm – 6/6pole 6AT8000-2AA00-1AE5 Length 450 cm – 4/6pole 6AT8000-2AA10-1AE5 Further information is available from your local Siemens office and from the homepage www.siemens.com/siplus-cms. SIPLUS CMS4000 IFN AI-D Operating Instructions, 07/2021, A5E32612781A-AB...
  • Page 35: Dimensional Drawing

    Operating Instructions SIPLUS CMS4000 IFN AI-D Dimensional Drawing SIPLUS CMS4000 IFN AI-D Operating Instructions, 07/2021, A5E32612781A-AB...
  • Page 36: Service & Support In The Internet

    Operating Instructions SIPLUS CMS4000 IFN AI-D Service & Support in the Internet In addition to our documentation pool we offer our complete knowledge base on the In- ternet: www.siemens.com/automation/service&support There you find:  The newsletter, which is constantly updated to provide you with the latest information about your products.

Table of Contents