Rheem RIWH09AVFJ Design & Technical Manual page 86

Multi: 5 rooms type
Hide thumbs Also See for RIWH09AVFJ:
Table of Contents

Advertisement

Work method when reinforcing the heat insulation of on-site piping
Slit of heat insulating material
facing upward
Covered gas
pipe (heat
insulation
strengthened)
Heat insulating material
(procured at the site)
Condition
When the
If the cold or warm air blown out from the air conditioner
remote
directly contacts the thermostat section of the remote
controller
controller, the outlet temperature of the air conditioner
installation site
may be sensed and room temperature control will be
is bad.
different from the room temperature, and "not cooled" or
"not heated" or other trouble may occur.
In addition, there is the possibility that the same kind of
trouble may also occur when the remote controller is
effected by direct sunlight.
When
When the wall mounted type was installed in a bedroom,
installation
living room, or other quiet place, the sound of the
environment is
refrigerant flow may be sensed as noise and must be
quiet.
taken into account.
When using the
Signals may not be received when using it in a room
wireless
illuminated by an inverter fluorescent lamp.
remote
controller.
When installing
It may generate noise in TV sets, stereos and PCs.
the inverter
type.
Heat insulation reinforcement material
Flare connection
(procured at the site)
Small exposed part
Binding material
of copper pipe is desirable.
Fig. B
Contents
- 80 -
To indoor unit
Fit tightly
(purpose is to cover the sealant)
Countermeasures (Reference)
1. Install the remote controller
where it will not be directly
exposed to the cold or hot air.
2. Install the remote controller
where it will not be directly
exposed to sunlight or strong
lighting.
1. Plan installation of a model
with external expansion valve.
2. Plan installation of a branch
box farther from indoor unit.
3. Plan installation using another
air conditioner.
Turn on the fluorescent lamp and
check if the indoor unit receives the
signals from the remote controller.
If the indoor unit does not receive
the signals, consult an authorized
service personnel.
The inverter type should be
installed at a sufficient distance
from these equipments.