Emerson Vilter PLC Operation Manual page 82

Blower package
Table of Contents

Advertisement

Section 11 • Alarms, Trips, Status Information & Troubleshooting
Trip Message
(T107) Alarm: Lower Inlet Scrubber
High High Level
(T108) Trip: (Unassigned)
(T109) Trip: (Unassigned)
(T110) Trip: (Unassigned)
(T111) Alarm: Outlet Scrubber High
High Level
(T112) Alarm: Outlet Scrubber Low
Low Level
(T113) Trip: (Unassigned)
(T114) Alarm: Upper Outlet
Scrubber High High Level
(T115) Trip: (Unassigned)
(T116) Trip: (Unassigned)
(T117) Alarm: Lower Outlet Scrubber
High High Level
(T118) Trip: (Unassigned)
(T119) Trip: (Unassigned)
(T120) Trip: Out Of Range: Suction
Header Pressure
(T121) Trip: Out Of Range: Blower 1
Suction Pressure
(T122) Trip: Out Of Range: Blower 1
Discharge Pressure
(T123) Trip: Out Of Range: Blower 1
Discharge Temperature
(T124) Trip: Out Of Range: Blower 1
Phase A Temperature
(T125) Trip: Out Of Range: Blower 1
Phase B Temperature
(T126) Trip: Out Of Range: Blower 1
Phase C Temperature
11 – 14
Cause(s)
Inlet Scrubber Lower Section High
High Liquid Level Switch Activated
(Selected Action = TRIP)
Outlet Scrubber High High Liquid
Level Switch Activated (Selected
Action = TRIP)
Outlet Scrubber Low Low Liquid
Level Switch Activated (Selected
Action = TRIP)
Outlet Scrubber Upper Section High
High Liquid Level Switch Activated
(Selected Action = TRIP)
Outlet Scrubber Lower Section High
High Liquid Level Switch Activated
(Selected Action = TRIP)
Pressure Instrument is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
Pressure Instrument is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
Pressure Instrument is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
Notes
Active if Coalescing Type Inlet
Scrubber is present
Active if Vane Type Outlet Scrubber
is Present
Active if Vane Type Outlet Scrubber
is Present
Active if Coalescing Type Outlet
Scrubber is present
Active if Coalescing Type Outlet
Scrubber is present
Active if Suction Header Pressure is
Being Monitored
Active if Winding Temperatures are
being monitored.
Active if Winding Temperatures are
being monitored.
Active if Winding Temperatures are
being monitored.