Section 8 • Alarm and Trip Setpoints

Alarm and Trip Setpoints

Screens may have inverted colors for ease of
readability.
The blower controller continuously monitors opera-
tional and process data and annunciates an alarm and/
or shuts the blower down if any condition becomes ab-
normal. The alarm and trip points for some of the op-
erational and process data are adjustable by the user in
the alarm and trip setpoints screens. The alarm and trip
setpoints are interlocked such that a low alarm may not
be set lower than a low trip, and a high trip may not be
set below a high alarm.
Actual values of the specifi c operational and process
data is shown in the column in the middle of the screen.
Setpoints are only shown for applicable alarm and trip
points.
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
NOTE
Figure 8-1. Alarm and Trip Setpoints Screen - 1 of 2
Alarm and Trip Setpoints - Page 1
• Suction Pressure: Low Alarm and Low Trip setpoints
for suction pressure at the individual blower or head-
er (if selected).
• Discharge Pressure: High Alarm and High Trip set-
points for discharge pressure at the individual blower
or header (if selected).
• Discharge Temperature: High Alarm and High Trip
setpoints for blower discharge temperature.
• Motor Winding Temperature: High Alarm and High
Trip setpoints for temperature of the main motor
windings, if motor winding RTDs are installed.
• Motor Bearing Temperature: High Alarm and High
Trip setpoints for temperature of the main motor
bearings, if motor bearing RTDs are installed.