Section 11 • Alarms, Trips, Status Information & Troubleshooting
Trip Message
(T153) Trip: Out Of Range: Blower 4
Phase C Temperature
(T154) Trip: Out Of Range: Blower 4
ODE Temperature
(T155) Trip: Out Of Range: Blower 4
DE Temperature
(T156) Trip: Out Of Range: Blower 4
Motor Amps
(T157) Trip: Unassigned
(T158) Trip: Unassigned
(T159) Trip: Unassigned
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
Cause(s)
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
RTD Input is Disconnected or Raw
Value is less than 3.5 mA or greater
than 20 mA (If using 4-20mA
Transmitter)
Motor Amps input is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
Notes
Active if Winding Temperatures are
being monitored.
Active if Bearing Temperatures are
being monitored.
Active if Bearing Temperatures are
being monitored.
11 – 17