Operating
Description
Mode
NO
Measurement not being updated. Device defaults
SERVICE
to Fail-safe mode
LEVEL
Distance to material surface.
SPACE
Distance to material surface.
DISTANCE Distance to material surface.
1)
For more details on Fail-safe Mode see the full manual.
1.6. Low Calibration Point
Distance from Sensor Reference to Low Calibration Point: usually process empty level. See
Operating Mode (1.5.) for an illustration.
Range: 0.00 to 20.00 m
Values
1.7. High Calibration Point
Distance from Sensor Reference to High Calibration Point: usually process full level. See
Operating Mode (1.5.) for an illustration
Range: 0.00 to 20.00 m
Values
1.8. Apply? (Apply changes)
In order to save the Quick Start settings it is necessary to select Yes to apply changes.
Options
Press Mode
to return to Measurement mode. SITRANS LR200 is now ready to operate.
Communications via PROFIBUS PA
Notes:
• The following instructions assume that the user is familiar with PROFIBUS PA.
• You will need the full manual to acquire the list of applicable parameters.
• Application Guides for setting up PROFIBUS PA devices with SIMATIC PDM can be down-
loaded from the product page of our website at: www.siemens.com/LR200 under Support.
Configuring the PROFIBUS PA master
To configure SITRANS LR200 on the network, you will need the GSD file SIEM810F.gsd. You can
download the file from the product page of our web site at: www.siemens.com/LR200. Go to
Support > Software Downloads.
SIMATIC PDM
We recommend that you use SIMATIC Process Device Manager (PDM) to program your
device. Please consult the operating instructions or online help for details on using SIMATIC
PDM. You can find more information at www.siemens.com/simatic-pdm.
A5E32153438
SITRANS LR200 (PROFIBUS PA) – QUICK START MANUAL
1)
.
.
YES, NO, DONE (Display shows DONE when Quick Start is successfully
completed.)
Reference point
Low Calibration Point
High Calibration Point
Sensor Reference Point.
Page EN-17