Quick Start Wizard via the handheld programmer
1.
Quick Start
a)
Point the programmer at the display from a maximum distance of 300 mm (1 ft) then press
RIGHT arrow
b)
Press RIGHT arrow
c)
Press RIGHT arrow
and move directly to the next item.
d)
To change a setting, scroll to the desired item or key in a new value.
e)
After modifying a value, press RIGHT arrow
to move to the next item.
f)
Quick Start settings take effect only after you select Yes to Apply changes in step 1.8.
1.1. Language
Selects the language to be used on the LCD and takes effect immediately.
ENGLISH, DEUTSCH, FRANÇAIS, ESPAÑOL
Options
1.2. Material
LIQUID
Options
LIQUID LOW DK (low dielectric liquid - CLEF algorithm enabled)
1.3. Response Rate
Sets the reaction speed of the device to measurement changes in the target range.
Response Rate
SLOW
MED
FAST
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
1.4. Units
Sensor measurement units.
M, CM, MM, FT, IN
Options
1.5. Operating Mode
space
level
Page EN-16
SITRANS LR200 (PROFIBUS PA) – QUICK START MANUAL
to activate PROGRAM mode and open menu level 1.
twice to navigate to menu item 1.1 and open parameter view.
to open Edit mode or
Fill Rate/Empty Rate
0.1 m/minute (0.32 ft/min)
1.0 m/minute (3.28 ft/min)
10.0 m/minute (32.8 ft/min)
distance
High Calibration
Point
(process full
level)
to accept default values
DOWN arrow
to accept it and press
sensor reference point
Low Calibration Point
(process empty level)
DOWN arrow
A5E32153438