Omron Sysmac NYB-0 Series Hardware User Manual page 165

Industrial pc platform, industrial box pc
Table of Contents

Advertisement

2
For Box PCs that do not have Windows pre-installed: Download the above mentioned soft-
ware.
3
Wire the S8BA UPS.
1) Wire the input of the UPS to the output of the Power Supply.
2) Wire the output of the UPS to the power connector of the Box PC.
3) Ground the UPS.
4) Connect the Contact port of the S8BA UPS to the I/O port of the Box PC with the connec-
tion cable S8BW-02.
Power Supply (S8VK)
AC (L)
AC (N)
4
Power ON the Box PC.
5
Configure the UPS.
1) Connect the USB cable supplied with the UPS to the USB connector of the UPS and to the
USB connector of the Box PC.
2) Configure the UPS using the UPS Settings Utility.
Refer to UPS Setting Utility Instruction Manual for S8BA/BU-2RWL for details.
3) Remove the USB cable between the UPS and the Box PC
6
Configure the Box PC to auto-start after power loss within the BIOS settings.
Refer to A-1 BIOS on page A-2 for BIOS details.
7
Create a software program that monitors the UPS Mode Input and initiates Power OFF of the
Box PC when the UPS Mode Input becomes active.
If the Box PC has a Windows operating system then use the Industrial PC System API to cre-
ate the software program.
Refer to NY-series Software Development Kit User's Manual for API details.
8
Install the created software program.
9
Test the created software program and ensure it functions correctly.
10
Simulate a power interruption and confirm a correct shutdown of the Box PC.
NY-series Industrial Box PC Hardware User's Manual (W553)
UPS (S8BA)
24 VDC
Input
24 VDC
0 VDC
Output
24 VDC
0 VDC
COM
4
BU
1
6
BS
Contact
5 Installation
IPC Product
6
UPS Mode Input
5
UPS Mode Input
2
Power Status Output
1
Power Status Output
I/O
5-51
5

Advertisement

Table of Contents
loading

Table of Contents