Fig. 11
Guided start-up
NOTE:
You may cancel any action by pressing the = button.
Cancelling of operation returns user interface view one
level up in menu hierarchy.
5.3

Configuration menu

The local user interface is organised in a menu struc-
ture. To enter the menus press + and - simultaneously
in the measurement monitoring view panel. To move to
the next or previous selection by pressing + or -
accordingly.
5.4

Mode menu

If the user wants to change the valve operating mode,
press the ? key at the MODE selection. The mode will
start to flash and by pressing + or - you may alter the
operation mode selection. User accepts the current
selection by pressing the ? key.
There are two options for the operating mode.
5.4.1 AUTO
During the auto mode, the controller controls the valve
position according to the incoming setpoint signal from
the bus. This mode is used during the normal process
control service.
— brief push
Fig. 12
Configuration
5.4.2 MAN
During this mode the valve position may be controlled man-
ually by using the keyboard and pressing the + or - but-
tons. The position of the manually driven valve is not saved
in the memory of the controller, i.e. the valve will not return to
the same position after signal failure. However, the valve
may be driven back into position after signal failure by
using + and - keys.The manual control starts from the
current position of the valve after the MAN-mode is acti-
vated. In order to change the manual setpoint return to the
measurement monitoring view and go to target position
measurement. Press the ? key shortly to activate the tar-
get position editing, text TPOS starts to blink and now you
are able to edit the setpoint by pressing + or - button.
The setpoint changes in 0.1 % increments/decrements in
spite of the selected unit and the valve starts to move
immediately. A continuous push changes the setpoint
faster. In order to view other measurements, press the ?
or = keys and select a measurement. Repeat the previ-
ous steps if you would like to alter the setpoint value again.
7 ND91P 70 en
— brief push