Class 7 Status Codes - Fronius Primo 3.0-1 Operating Instructions Manual

Hide thumbs Also See for Primo 3.0-1:
Table of Contents

Advertisement

Available languages

Available languages

Code
Description
Insulation error on the solar
502
modules
No energy fed into the grid in
509
the past 24 hours
Unable to communicate with
515
filter
No communication possible
516
with the storage unit
Power derating caused by too
517
high a temperature
522
DC low String 1
523
DC low String 2
Functional incompatibility (one
or more PC boards in the in-
558
verter are not compatible with
each other, e.g. after a PC
board has been replaced)
Power derating caused by
560
overfrequency
566
Arc detector switched off
(e.g. during external arc moni-
toring)
Class 7 status
Class 7 status codes relate to the control system, the configuration and inverter data re-
codes
cording, and may directly or indirectly affect the process of feeding energy into the grid.
Code
Description
Conflict when setting the in-
705
verter number (e.g. number al-
ready assigned)
EEPROM has been reinitial-
721
ised or EEPROM is faulty
46
Behaviour
Warning message is shown on
the display
Warning message is shown on
the display
Warning message on the dis-
play
Storage unit warning message
When power derating occurs, a
warning message is shown on
the display.
Warning message on the dis-
play
Possible error displays or mal-
functions on the inverter
This status code is displayed
when the grid frequency be-
comes excessively high.
The inverter will then reduce its
output.
The status indicator will contin-
ue to be displayed until the in-
verter has returned to normal
operation.
The status code is displayed
every day until the arc detector
is reactivated.
Behaviour
-
Warning message is shown on
the display
Remedy
If this status code keeps recur-
ring, contact your system engi-
neer.
Acknowledge status code;
check whether all the condi-
tions for the problem-free feed-
ing of energy into the grid have
been met (e.g. are the solar
modules covered with snow)
If the status code is displayed
all the time: look out for further
status codes
If the status code is displayed
all the time: Notify a Fronius-
trained service technician.
Purge openings for cooling air
and heat sink if necessary;
fault is rectified automatically;
if this status code keeps recur-
ring, contact your system engi-
neer
If this status code keeps recur-
ring, contact your system engi-
neer.
If this status code keeps recur-
ring, contact your system engi-
neer.
As soon as the grid frequency
is back within the permissible
range and the inverter has re-
turned to normal operation, the
fault is rectified automatically.
If this status code keeps recur-
ring, contact your system engi-
neer.
No error
Confirm status code by press-
ing 'Enter'
Remedy
Correct the inverter number via
the Setup menu
Acknowledge status code;
If the status code is displayed
all the time: notify a Fronius-
trained service engineer

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents