Set 7 - Siemens MJ-4 Series Installation Manual

Communications module, fiber optic and rs-232/485, for mj-4a, mj-xl and mj-x control panels
Table of Contents

Advertisement

8.2.8 Set 7

Binary Inputs
Point #
Description
0
Auto Inhibit Status
1
Remote Switch position
2
Manual Switch position
3
Neutral (U12) Signal
4
Power Flow Direction
Binary Outputs
Point #
Description
0
Tap Raise
1
Tap Lower
2
Auto Inhibit (On/Off)
Analog Inputs
Point #
Description
0
Tap Position
1
Load Voltage
2
Load Current
3
Source Voltage
4
kW Load
5
kVA Load
6
kVAR Load
7
Op Count Last Month
8
Op Count Month-to-Date
9
Maintain Records of Contacts
10
Tap Changer Type
11
Balance Winding
12
Range of Regulation
13
Lower Led Solid/Blink
14
U2-P2 Terminal Out
15
Fixed RL On time
16
Log Min Max
17
PT Calc Enable
Analog Outputs
Point #
Description
0
Fwd Voltage Level
1
Fwd Bandwidth
2
Fwd Time Delay
3
Clear Contact Statuses and Op Counters
4
Read Overall Status of Contacts
8.2.9 2.x3
Binary Inputs
Point #
Scale Factor
0
SF = 1
1
SF = 1
2
SF = 1
3
SF = 1
4
SF = 1
5
SF = 1
6
SF = 1
7
SF = 1
8
SF = 1
9
SF = 1
Description
Tap Pos Known
Power Flow Direction
Auto Inhibit Status
Raise (J) Motor Signal
Lower (K) Motor Signal
Remote Control occurring
U2/P2 Switch Position
Neutral (U12) Signal
Operations Count (U10) Signal
Auto Inhibit Terminal Block Input
MJ-4 Communications Module
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mj-4aMj-4b

Table of Contents