Figure 13-4. Sd Card Replacement - Emerson Vilter MicroVission Operation And Service Manual

Hide thumbs Also See for Vilter MicroVission:
Table of Contents

Advertisement

Section 13 • Data Backup
Replace SD card
1. Power down the MicroVission panel.
2. Remove old SD card and install new SD card.
3. Power up the MicroVission panel.
Re-Enter Operating Setpoints And Configuration
Information
1. Logon as "admin" user (default password = admin).
2. Re-enter all values in Configuration screen. The
most vital thing is to re-enter the correct No. of Cyl-
inders and No. of Unloaders. Re-enter the Compres-
sor Runtime on page 2 of the configuration screen.
Ensure you re-select any optional boards that are
installed, and apply those additions.
3. Re-enter all Control Limits.
4. Re-enter all Alarm and Trip setpoints. The most vital
thing is - under the "Delay" tab, enter 5 seconds for
all alarm and trip delays.
5. Re-enter all Timer Setpoints.
6. Re-enter all Instrument Calibration offsets for pres-
sure transducers. Insure that the Suction Pressure
transducer range is properly selected (typically
0-200psia 4-20mA) – but double check proper set-
ting.
13 – 6

Figure 13-4. SD Card Replacement

MicroVission Controller • Operation and Service Manual • Emerson • 35391MV