3.5 – Compressor Rotation
It is important to be certain the compressors are rotating in the proper direction. To determine whether or not
compressors are rotating in the proper direction:
1. Connect service gages to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in the wrong direction.
2. Turn off power to the unit.
3. Reverse any two of the compressor lead wires.
4. Turn on power to the compressor.
5. Check also phase monitor all ok green led before proceeding.
The suction and discharge pressure levels should now move to their normal start-up levels.
For wire runs up to 50 ft, use no. 18 AWG insulated wire. For 50 to 75 ft, use no. 16 AWG insulated wire. For over 75 ft, use no.
14 AWG insulated wire. All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a

3.6 - Evaporator Fan

Fan belt and variable pulleys are factory installed. Remove tape from the fan pulley. See Table 4 Fan Performance
data. Be sure that fans rotate in the proper direction. See Table 3 Fan RPM at various fan motor pulley settings. To
alter fan performance, see Evaporator Fan Performance Adjustment section.
3.7– Condenser Fans and Motors
Fans and motors are factory set. Refer to Condenser-Fan Adjustment Section as required.
3.8– Return – Air Filters
Check that correct filters are installed in filter tracks. See Table 1 Physical data. Do not operate unit without return
air filters.
3.9 – Base Unit Operation
COOLING, UNITS — when thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator)
fan contactor (IFC), and compressor contactor no. 1 (C1) are energized and evaporator-fan motor, compressor no. 1
and condenser fans start. The condenser-fan motors run continuously while unit is cooling. If the thermostat calls for
a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2
starts.
HEATING, UNITS — (If Accessory or Optional Heater is installed) — upon a call for heating through terminal W1,
IFC and heater contactor no. 1 (HC1) are energized.
NOTE
IMPORTANT
junction box and splice at the thermostat.