Positioning And Clearance - Carrier 50TCM Series Installation, Operation And Maintenance Manual

Package rooftop units - 50hz, nominal cooling capacity 6 - 12.5 tons, hfc r-410a refrigerant
Table of Contents

Advertisement

Roof mount - Check building codes for weight distribution requirements. Unit weight and dimensions is shown in unit
dimensional drawing and Table 2.
UNIT
50TCMA07
50TCMD08
50TCMD09
50TCMD12
50TCMD14
NOTES:
1. Remove boards at ends of unit and runners prior to rigging.
2. Rig by inserting hooks into unit base rails as shown. Use bumper boards for spreader bars.
Crub should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are shown in Fig.3
IMPORTANT
All units are internally isolated against
vibration. If extra isolation required, please see
"Unit Dimensional Drawing"
2.5 – Positioning and Clearance
Before positioning the unit, check the following:
The permitted loading at the site is adequate or that appropriate strengthening measures have been taken.
The unit is installed level on an even surface.
Ensure access to the components (see "Unit Dimensional Drawings" & "Clearance Diagram" Fig 1).
The number of support points is adequate and that they are in the right places.
Although the unit is weatherproof guard against water from higher level runoff and overhangs.
Unit may be installed directly on wood flooring or on approved roof - covering material when roof curb is used. Do not
install unit in an indoor location. Do not locate air inlets near exhaust vents or sources of contaminated air.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are shown in Fig.3
Max Weight
LB
KG
IN
645
293
74.4
1410
641
88.0
1525
693
88.0
1565
711
88.0
1720
782
88.0
Table – 2 Unit Weights and Dimensions
Fig. 3 Unit Leveling Tolerance
NOTE
Fig. 3 Unit Leveling Tolerance
DIMENSIONS
A
B
MM
IN
MM
1888
38.0
965
2235
41.0
1040
2235
40.5
1030
2235
40.0
1015
2235
28.5
725
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
All panels must be in place when rigging.
Page 13
C
IN
MM
41.4
1051
41.5
1055
49.5
1255
49.5
1255
53.0
1345
CAUTION