11.6 Connection Diagrams - Metso Neles SwitchGuard SG9200H Installation Maintenance And Operating Instructions

Table of Contents

Advertisement

30

11.6 Connection diagrams

See Section 8.1.3 for additional limit switch data.
SG92_H/I02, I09
OPEN
CLOSED
Factory adjustment:
Active faces of proximity switches are covered when actuator is in intermediate position.
Active face A (upper switch) becomes free at open limit of travel and face K (lower switch) at closed limit.
Function can be inverted on site by re-adjusting the cam discs.
Sensing distance 2...4 mm, depending on type of switch
Supply voltage 8 V DC (Ri 1 kΩ)
Current consumption
active face free, > 3 mA
active f ace covered, < 1 mA
PROXIMITY SWITCH
Intrinsically safe II 2 G EEx ia IIC T6.
According to CENELEC EN50014 and EN50020.
Voltage (Ui), current (Ii), power (Pi), inductance (Li) and
capacitance (Ci) according to certificate of switch, see table below.
Type of proximity switch
02
P+F NJ2-12GK-SN
09
P+F NCB2-12GM35-N0
BLUE
11
A
BROWN
13
BLUE
14
K
BROWN
16
Electrical values
Ui
Ii
(V) (mA)
(mW)
16
52
169
16
52
169
Ex classification
Pi
Li
Ci
(µH) (nF)
150
50
II 2 G EEx ia IIC T6
100
90
II 2 G EEx ia IIC T6
7 SG92H 70 en
Certificate
PTB 00 ATEX 2049 X