To Install The Outdoor Unit; To Provide Drainage - Daikin Altherma EJHA04AAV3 Installer's Reference Manual

Hybrid hydrosplit heat pump
Hide thumbs Also See for Altherma EJHA04AAV3:
Table of Contents

Advertisement

9 Installation
Anchor points
(mm)
574
Option 1: On mounting feet "flexi-foot with strut"
(mm)
a
Maximum snowfall height
Option 2: On plastic mounting feet
Option 3: On a pedestal
(mm)
Installer reference guide
32
4× M8/M10
Option 4: On brackets to the wall
(mm)
a
Anti-vibration rubber (field supply)
9.3.4

To install the outdoor unit

9.3.5

To provide drainage

▪ Make sure that condensation water can be evacuated properly.
▪ Install the unit on a base to make sure that there is proper
drainage in order to avoid ice accumulation.
▪ Prepare a water drainage channel around the foundation to drain
waste water away from the unit.
▪ Avoid drain water flowing over the footpath, so that it does NOT
become slippery in case of ambient freezing temperatures.
▪ If you install the unit on a frame, install a waterproof plate within
150  mm of the bottom side of the unit in order to prevent water
from getting into the unit and to avoid drain water dripping (see the
following figure).
Daikin Altherma Hybrid hydrosplit heat pump
a
4× M8/M10
EJHA04AAV3 + EHY2KOMB28+32AA
4P531180-1 – 2018.06