10 Configuration
INFORMATION
Solar panels. If solar panels are used, set the electricity
price value very low to promote the use of the heat pump.
Space heating control
The basic required settings in order to configure the space heating of
your system are described in this chapter. The weather-dependent
installer settings define the parameters for the weather-dependent
operation of the unit. When weather-dependent operation is active,
the water temperature is determined automatically depending on the
outdoor temperature. Low outdoor temperatures will result in warmer
water and vice versa. During weather-dependent operation, the user
has the possibility to shift up or down the target water temperature
by a maximum of 10°C.
See the user reference guide and/or operation manual for more
details about this function.
Leaving water temperature: Main zone
#
Code
[A.3.1.1.1]
N/A
LWT setpoint mode:
▪ 0 Fixed: The desired leaving water
temperature is:
▪ NOT weather-dependent (i.e. does
▪ fixed in time (i.e., NOT scheduled)
▪ 1 Weather dep.: The desired leaving
water temperature is:
▪ weather-dependent (i.e. depends
▪ fixed in time (i.e., NOT scheduled)
[A.3.1.1.1]
N/A
<< continuation
▪ 2
leaving water temperature is:
▪ NOT
▪ according
▪ 3
leaving water temperature is:
▪ weather-dependent
▪ according
Installer reference guide
60
Description
NOT
depend
on
the
outdoor
ambient temperature)
on
the
outdoor
ambient
temperature)
continued >>
Fixed/scheduled:
The
desired
weather-dependent
(i.e.,
does NOT depend on the outdoor
ambient temperature)
a
schedule.
The
scheduled
actions
consists
desired shift actions, either preset
or custom.
Remark: This value can only be
set in leaving water temperature
control.
WD/scheduled:
The
desired
(i.e.,
does
depend on the outdoor ambient
temperature)
a
schedule.
The
scheduled
actions
consists
desired
leaving
water
temperatures
either
preset
custom
Remark: This value can only be
set in leaving water temperature
control.
#
Code
[7.7.1.1]
[1‑00]
[1‑01]
[1‑02]
[1‑03]
[7.7.1.1]
[1‑00]
[1‑01]
[1‑02]
[1‑03]
INFORMATION
In order to optimise comfort as well as running costs, it is
recommended to choose weather-dependent setpoint
operation. Set the settings carefully; they have significant
of
influence on heat pump as well as boiler operation. Too
high leaving water temperature can result in constant boiler
operation.
NOTICE
In case of third-party gas boiler:
If you use weather-dependent operation, make sure to set
the values for the weather-dependent curves twice for
correct operation:
▪ Once on the user interface of the outdoor unit
▪ Once on the third-party gas boiler
of
or
Description
Set weather-dependent heating:
T t
[1-02]
[1-03]
[1-00]
[1-01]
▪ T
: Target leaving water temperature
t
(main)
▪ T
: Outdoor temperature
a
continued >>
<< continuation
▪ [1‑00]:
Low
outdoor
temperature. –40°C~+5°C
▪ [1‑01]:
High
outdoor
temperature. 10°C~25°C
▪ [1‑02]:
Desired
leaving
temperature
when
the
temperature equals or drops below
the low ambient temperature.
[9‑01]°C~[9‑00]°C
Note: This value should be higher
than [1-03] as for low outdoor
temperatures
warmer
water
required.
▪ [1‑03]:
Desired
leaving
temperature
when
the
temperature equals or rises above
the high ambient temperature.
[9‑01]°C~min(45, [9‑00])°C
Note: This value should be lower
than [1-02] as for high outdoor
temperatures less warm water is
required.
EJHA04AAV3 + EHY2KOMB28+32AA