Symbolic Name Assignment - Siemens SIMATIC PCS 7 Configuration

Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

3 Configuring the redundant peripherals

3.8 Symbolic name assignment

Activity
3.
The HART field device is opened in
SIMATIC PDM. Here you can adjust other
device parameters (such as TAG).
4.
Select again the HART field device in the
hardware catalog and drag-and-drop it into
a free slot of the redundant partner (HART
signal module of the second ET 200M).
After a brief loading, the configured field
device of the first ET 200M is automatically
assigned.
3.8
Symbolic name assignment
For the symbolic name assignment it is assumed that the input/output modules
have been already added in the HW ConFigure Once this is done, you can assign
self-explanatory symbolic names to the inputs and outputs of these modules.
You use these names to connect CFC charts with the input and output modules.
Requirements
The PCS 7 project with an H CPU has been created and is open in SIMATIC
Manager.
A redundant PROFIBUS-DP master system is configured for the SIMATIC
H station in HW ConFigure
In HW Config, the interface module IM 153-2 is configured for the ET 200M
at the redundant PROFIBUS DP.
All required signal modules are configured.
The redundant ET 200M has been configured.
The settings on the signal module have been done
Configuration of Redundant I/O Modules
Entry-ID: 28430682,
V2.0,
03/2015
Screenshot
56

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents