3 Configuring the redundant peripherals

3.5 Signal module settings

3.5
Signal module settings
Once you have configured both ET 200M stations, you have to change various
settings in your standard and HART signal modules.
Redundant modules must be in the process image of the inputs or outputs.
Redundant modules are always accessed using the process image.
Requirements
The PCS 7 project with an H CPU has been created and is open in SIMATIC
Manager.
A redundant PROFIBUS-DP master system is configured for the SIMATIC
H station in HW ConFigure
In HW Config, the interface module IM 153-2 is configured for the ET 200M
at the redundant PROFIBUS DP.
All required signal modules are configured.
The redundant ET 200M has been configured.
Procedure
Table 3–5
Activity
1.
Open HW KonFigure
Select once again the first
IM 153-2.
Double-click a signal module in the module
overview. The dialog box "Properties" of
this module is opened.
2.
Switch to the "Addresses" tab.
Select the desired process image partition
from the drop-down list "Process image".
Configuration of Redundant I/O Modules
Entry-ID: 28430682,
V2.0,
03/2015
Screenshot